background image

COMMISSIONING

THE ORGANISATION RESPONSIBLE FOR THE COMMISSIONING SHALL BE RESPONSIBLE 

FOR PROPER MOTOR PHASING AND STARTING PATTERN SELECTION.

•  After fan starting make sure that the electric motor rotates properly without undue vibration and abnormal noise. 
•  Make sure that the fan impeller rotates in the direction marked by the arrow on the fan casing. If necessary, change the rotation 

direction of the impeller by reversing the phase sequence (for a three-phase motor) or by rewiring according to the wiring diagram 
located inside the terminal box (for a single-phase motor).

•  Make sure that the fan energy consumption complies with the value given on the equipment nameplate and check the motor for 

overheating.

•  The phase current should be checked once the fan reaches the rated operating conditions.
•  Do not switch the fan on and off several times without pauses as this may result in damage to the winding or insulation due to 

overheating. 

DURING STARTING THE IN-RUSH CURRENTS OF THE FAN MAY SEVERAL TIMES EXCEED 

THE RATED VALUES. 

SEE “ASYNCHRONOUS ELECTRIC MOTOR STARTING METHODS” IN THE “CONNECTION 

TO POWER MAINS” SECTION

Problems associated with DOL starting

The problems caused by DOL starting may be divided into two groups:
1.  An abrupt start causes mechanical shock, jolts in the mechanism, shock removal of free play etc.
2.  A heavy start cannot be completed.

Let us review three variations of a heavy start:

1. The feed line performance is barely sufficient or insufficient to maintain the induced current.

Typical symptoms: 

Upon starting the circuit breakers at the system input are tripped; the lights, certain relays and contactors go off, 

and the supply generator shuts down.

Solution: 

In the best-case scenario an SS device may help reduce the in-rush current to 250 % of the motor rated current. If this is 

insufficient, an FC is necessary.

2. The motor cannot start the mechanism with DOL starting.

Typical symptoms: 

The motor fails to turn or “freezes” at certain speed which is maintained until actuation of the protection suite.

Solution: 

This problem may not be solved with an SS device. The motor develops insufficient shaft torque. However, this problem can 

be addressed by using an FC, but each case may be different.

3. The motor spins up the mechanism with authority, but fails to reach the rated rotation speed.

Typical symptoms: 

The input automatic circuit breaker is tripped during spin-up. This often happens with heavy-weight fans with a 

considerable rotation speed.

Solution: 

Such problems may be addressed with an SS device, but not with 100 % certainty. The closer the motor speed to the rated 

value during the actuation of the protective equipment, the higher the chances of success. The use of an FC in this case helps solve the 
problem fundamentally.

Standard switching equipment (automatic circuit breakers, contactors and motor starters) is not designed to withstand 

prolonged overloads normally causing the fan to shut down automatically DOL starting that continues for a long period of 

time.

Using switching equipment with a higher maximum current rating renders the electric motor protection system less sensitive. 

As a result the switching equipment will not be able to detect motor overload in time due to a high current sensing threshold.

Such problems as mentioned above can only be addressed by utilizing a soft starter or a frequency converter to start the fan.

www.blaubergventilatoren.de

tower-sV-k2

13

Summary of Contents for Tower-SV-K2

Page 1: ...Roof mounted centrifugal smoke extraction fan USER S MANUAL EN Tower SV K2...

Page 2: ...al and national construction electrical and technical norms and standards must be observed when installing and operating the unit Disconnect the unit from the power supply prior to any connection serv...

Page 3: ...ck of experience and knowledge unless they have been given supervision or instruction concerning use of the unit by a person responsible for their safety Children should be supervised to ensure that t...

Page 4: ...nditions The fan handles smoke and air mixtures with temperatures up to 600 C for 60 minutes A characteristic feature of Tower SV K2 roof fans is an impeller with backward curved blades and an electri...

Page 5: ...U1 temperate climate HL1 cold climate T1 tropical climate M1 marine moderately cold climate Options K with a terminal box S1 built in external switch 1 5 motor power kW Motor phase and operation mode...

Page 6: ...0 75 2 15 910 8500 Tower SV K2 560 4D 3 X XX 600 2 XXX 3 0 6 48 1420 13000 Tower SV K2 630 8D 0 75 X XX 600 2 XXX 0 75 2 64 700 9000 Tower SV K2 630 6D 1 5 X XX 600 2 XXX 1 50 3 84 940 12500 Tower SV...

Page 7: ...Overall dimensions B A C H d 4 holes www blaubergventilatoren de Tower SV K2 7...

Page 8: ...0 75 K U1 600 2 Zn 1060 1010 750 1121 16 Tower SV K2 630 6D 1 5 K U1 600 2 Zn Tower SV K2 630 4D 5 5 K U1 600 2 Zn Tower SV K2 710 8D 1 1 K U1 600 2 Zn 1105 1180 980 1257 16 Tower SV K2 710 6D 2 2 K U...

Page 9: ...m the fan The fan delivery set may include a mounting frame available separately Install the mounting frame on a load carrying roof section true vertical inside a prepared opening The opening size mus...

Page 10: ...nal box located on the outer casing of the fan impeller located inside the support panel The motor with the impeller is rigidly fixed to the support panel Welded sheet steel construction The hub and c...

Page 11: ...gth and installation method Connection of the unit to the fixed power supply network must be carried out in accordance with the current regulations Caution The type of electrical connection is indicat...

Page 12: ...oth out the inrush the high startup torque has no adverse effects on the operation of the driven mechanism Soft start SS starting A soft starter gradually increases the voltage supplied to the motor f...

Page 13: ...ain relays and contactors go off and the supply generator shuts down Solution In the best case scenario an SS device may help reduce the in rush current to 250 of the motor rated current If this is in...

Page 14: ...OR TO COMMENCING ANY TECHNICAL MAINTENANCE PUT UP A PROHIBITORY SIGN ON THE FAN STARTING PANEL DO NOT SWITCH ON MEN AT WORK POSSIBLE MALFUNCTIONS AND THEIR ELIMINATION Problem Possible reasons Elimina...

Page 15: ...ace the fan with a unit of proper standard size The fan supplies less air than expected Wrong calculation of the ventilation network and wrong selection of the fan Re calculate the network parameters...

Page 16: ...ndling requirements applicable for the particular type of cargo The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanic...

Page 17: ...nation of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation The faults are eliminated by means of replacement or repair of the unit componen...

Page 18: ...www blaubergventilatoren de Tower SV K2 18...

Page 19: ...____________ is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Si...

Page 20: ...www blaubergventilatoren de B81 1EN 01...

Reviews: