Install the Wi-Fi antenna.
Manually adjust the swing of the louvre shutters.
CONDENSATE DRAINAGE ARRANGEMENT
The unit is equipped with a drain pump for timely removal of condensate from the unit. Connect the flexible hose going from the
pump outlet to the sewage system.
min 3°
U-trap (hydraulic lock)
Sewage system
min 50 mm
WARNING! To ensure water drainage, pipes should be mounted with a slope of at least 3°.
Provide free drainage for the condensed water, otherwise it is accumulated inside the unit that may cause the equipment damage and
condensate outflow to the room. The condensate drainage system is designed for normal operation in premises with air temperatures
above 0 °C!
If the expected ambient air temperatures are below 0 °C the condensate drainage system must be equipped with heat insulation and
pre-heating facilities.
MOUNTING EXTERNAL VENTILATION GRILLES/HOODS
Fix the external ventilation grilles/hoods to the external wall of the building according to the supplied installation instructions.
The grilles are not included in the delivery set and can be purchased separately.