21
www.blaubergventilatoren.de
KOMFORT EC LB/LBE S11
Table 7. Error code description
Table 8. Default settings
Error code
Description
TE1
External temperature sensor malfunction.
TE2
Malfunction of the temperature sensor for heat exchanger freezing protection.
TE5
Duct temperature sensor malfunction.
TE6
Malfunction of the duct humidity sensor.
MIN
Supply fan malfunction.
MEX
Extract fan malfunction.
ERP
Control panel communication error.
DI1
Tripping of the overheat protection thermostat TK-60.
DI2
Fire alarm sensor actuation.
DI3
Tripping of the overheat protection thermostat TK-90.
ERROR CODE DESCRIPTION
DEFAULT SETTINGS
Parameter
Default setting
Air flow rate
1
Temperature
Duct
+ 25 °C
Room
+ 20 °C
Air flow setting
Air supply
Speed 1 - 40 %, Speed 2- 70 %, Speed 3 - 99 %
Air extract
Speed 1 - 40 %, Speed 2- 70 %, Speed 3 - 99 %
Temperature sensor
Duct
Extra options
Heating control
On
Supply Fan Off mode
Off
Humidity sensor selection
2
BYPASS Operation mode
1
Supply Fan Off mode
Working hours
20 minutes
Downtime
5 minutes
Switch-off temperature
+ 3 °C
Standby mode setting
Air flow rate
1
Temperature
+ 20 °C
Display brightness adjustment
Operation
50
Sleep
1
Humidity setting
Duct
50 %
Room
50 %
Temperature sensor correction
- 6 °C
Timer settings
Hours
01
Minutes
00
Air flow rate
1
Temperature
+ 20 °C
Motor hours
Setting
4000 hours
KOMFORT_EC_LBE_v1(3)_EN.indd 21