CONDENSATE DRAINAGE
Condensate drainage is required for the Komfort EC S5B270 S14 unit series. The Komfort EC S5B270-E S14 units are equipped with a heat
exchanger with an enthalpy membrane at the core. No condensate is formed in heat exchangers of this type, therefore, no condensate
drainage is required. The hole for the drain pipe connection is located at the bottom of the unit. Open the service panel, remove the heat
exchanger and filters, drill a hole (
7
/
8
inch in diameter) in a plastic pan in the exhaust air duct and install the drain pipe (supplied) in the
hole. Then connect the drain pipe to the sewage system using the SG-32 U-trap kit (purchased separately). The pipe slope downwards
must be at least 3°.
min 3°
Drain hose
U-trap
Sewage system
Drain pipe
The condensate drainage system is designed for normal operation in premises with air temperatures above 32 °F!
If the expected ambient air temperatures are below 32 °F, the condensate drainage system must be equipped with heat insulation and
pre-heating facilities.
SERVICE SIDE CHANGE
Right-handed installation Left-handed installation
Intake air
Intake air
Supply air
Supply air
Extract air
Extract air
Exhaust air
Exhaust air
Make sure of the correct unit service side selection. Unit mounting position should enable free excess to the opening plate for maintenance
and service operations. The plate opposite to the service side must be fixed with screws (included in the delivery set).
www.blauberg.us
Komfort EC S5B270(-E) S14
10