CONNECTION TO POWER MAINS

The air-handling unit is rated for connection to single-phase AC 120V/60 Hz power mains.  Connect the unit to power mains using the power 
cord with the IEC plug (included in the delivery set).
The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the circuit in the event 
of overload or short-circuit.  The position of the external circuit breaker must ensure free access for quick power-off of the unit.  The trip 
current must be in compliance with the consumption current, refer to Technical data.

Complete the electrical connections through the terminal block in the control unit as shown in the external wiring diagram.

Access to the control unit

External control units wiring diagram:

2

3

4

14

13

12

11

10

9

8

7

6

5

15

L

1

External device 
NO (CO2 sensor)

PK fire alarm panel 

(remove the jumper 

while connecting the contact)

120/60 Hz 

Control

 panel

- Tx Rx +

GND Tx

Rx +U

3

2

1

GND

+U

0-10V

GND

+U 0-10V

N

PE

РК

C

X1

16

SM-L

17

SM-N

Humidity 

sensor

W

hit

e

Bro

wn

Gr

een

Yello

w

XP

QF

Electric actuators 

of the external air dampers

SM1

supply

L1      N

SM2

exhaust

L1      N

Designation

Name

Model

Wire**

N.o

External control device contacts

LF230

2 x 20 AWG 

SМ1*

Supply air damper actuator

LF230

2 x 20 AWG

SМ2 *

Extract air damper actuator

LF230

2 x 20 AWG

РК*

Contact from fire alarm panel

NO

2 x 20 AWG

*    Is not included in the delivery set.
** Maximum connecting cable length is 20 m!

www.blauberg.us

MUI_83_Komfort EC S5B270 S14_EN-01

174 N. 36th Street, Lafayette, IN 47905
e-mail: info@blauberg.us

4

Summary of Contents for Komfort EC S5B270 S14

Page 1: ...ducts are too short or not connected protect the unit parts from ingress of foreign objects To prevent uncontrollable access to the fans the spigots may be covered with a protecting grille or other protecting device with mesh width not more than 1 2 inch While installing the unit ensure convenient access for subsequent maintenance and repair The unit must be mounted on a flat floor Installing the ...

Page 2: ...ing Fasteners dowels self tapping screws for wall mounting are not included in the delivery set and should be ordered separately Whilechoosingfastenersconsiderthematerialofthemounting surface as well as the weigh of the unit refer to the Technical data section Fasteners for unit installation should be selected by a qualified technician Secure the wall bracket at required height Hang the unit on th...

Page 3: ...n diameter in a plastic pan in the exhaust air duct and install the drain pipe supplied in the hole Then connect the drain pipe to the sewage system using the SG 32 U trap kit purchased separately The pipe slope downwards must be at least 3 min 3 Drain hose U trap Sewage system Drain pipe The condensate drainage system is designed for normal operation in premises with air temperatures above 32 F I...

Page 4: ...he external wiring diagram Access to the control unit External control units wiring diagram 2 3 4 14 13 12 11 10 9 8 7 6 5 15 L 1 External device NO CO2 sensor PK fire alarm panel remove the jumper while connecting the contact 120 60 Hz Control panel Tx Rx GND Tx Rx U 3 2 1 GND U 0 10V GND U 0 10V NО N PE PК РК C X1 16 SM L 17 SM N Humidity sensor White Brown Green Yellow XP QF Electric actuators ...

Reviews: