CONNECTION TO POWER MAINS
The air-handling unit is rated for connection to single-phase AC 120V/60 Hz power mains. Connect the unit to power mains using the power
cord with the IEC plug (included in the delivery set).
The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the circuit in the event
of overload or short-circuit. The position of the external circuit breaker must ensure free access for quick power-off of the unit. The trip
current must be in compliance with the consumption current, refer to Technical data.
Complete the electrical connections through the terminal block in the control unit as shown in the external wiring diagram.
Access to the control unit
External control units wiring diagram:
2
3
4
14
13
12
11
10
9
8
7
6
5
15
L
1
External device
NO (CO2 sensor)
PK fire alarm panel
(remove the jumper
while connecting the contact)
120/60 Hz
Control
panel
- Tx Rx +
GND Tx
Rx +U
3
2
1
GND
+U
0-10V
GND
+U 0-10V
NО
N
PE
PК
РК
C
X1
16
SM-L
17
SM-N
Humidity
sensor
W
hit
e
Bro
wn
Gr
een
Yello
w
XP
QF
Electric actuators
of the external air dampers
SM1
supply
L1 N
SM2
exhaust
L1 N
Designation
Name
Model
Wire**
N.o
External control device contacts
LF230
2 x 20 AWG
SМ1*
Supply air damper actuator
LF230
2 x 20 AWG
SМ2 *
Extract air damper actuator
LF230
2 x 20 AWG
РК*
Contact from fire alarm panel
NO
2 x 20 AWG
* Is not included in the delivery set.
** Maximum connecting cable length is 20 m!