OM-AF30 E V1.02
October 18, 2013
Page 11
ASHFORD 30
INSTALLATION INSTRUCTIONS cont.
MINIMUM CLEARANCES for AF30
G = 2.75” (76mm) in USA
8” (203mm) in Canada
H = 16” (406mm) in USA
18” (456mm) in Canada
I = 0” (0mm) in USA
8” (203mm) in Canada
K = 18” (456mm) for single wall pipe in Canada
(If K=18”, J=79.375” (2134mm) Minimum)
Ember protection shield (not required to have an insulation value)
is to be listed under UL 1618-2009 (type 1) and must have a minimum size of:
In USA: 42 1/8” x 35” (1070 x 889 mm)
In Canada: 52 1/8” x 45 1/2” (1324 x 1156 mm)
Min. Alcove minimum width 48”, maximum depth 48”, minimum height 72”
This stove must be installed in compliance with all local codes and regulations.
K
J
*3ft RECOMMENDED
MIN 2ft*
H
G
F
E
I
*1
*1
" in USA
5/8
" in Canada and 55
*1= 5
7/8
" in Canada and 2
1/8
" in USA
*2 = 57
5/8
*2
A
I
H
2"
D
C
B
G
G
Residential Installations
A
B
C
D
E
F
J
Roof exit, parallel and corner. No fan kit required.
10.75”
273mm
6”
153mm
25.5”
648mm
16.375”*
416mm
4”
102mm
16.875”*
429mm
72”
1829mm
Wall exit, parallel and corner. No fan kit required.
10.75”
273mm
6”
153mm
25.5”
648mm
16.375”*
416mm
4”
102mm
16.875”*
429mm
72”*
1829mm
Alcove, roof or wall exit. Use either fan kit or rear shield and double wall pipe.
10.75”
273mm
6”
153mm
25.5”
648mm
16.375”
416mm
72”
1829mm
Mobile Home Installation
Roof exit, parallel and corner. Use either fan kit or rear shield, double wall pipe
and outside air kit.
10.75”
273mm
6”
153mm
25.5”
648mm
16.375”
416mm
4”
102mm
16.875”
429mm
72”
1829mm
* Check with local codes and pipe manufacturer for pipe clearances. In Canada, 18” clearances from single wall pipe is required.