50
E
N
G
L
IS
H
Steps for Setting Up the Speed Controller
1 - Delivery of the speed controller
• Check that the speed controller reference printed on the label is the same as that on the delivery note
corresponding to the purchase order.
• Remove the BLEMO-ER21 from its packaging and check that it has not been damaged in transit.
2 - Fit the speed controller and attach its labels (page 51)
3 - Connect the following to the speed controller :
• The line supply, ensuring that it is volt free
• The motor, ensuring that the terminal configuration corresponds to the supply voltage
• The control via the logic inputs
• The speed reference via the logic or analog inputs
4 - Switch on the speed controller, but do not give a run command
5 - Configure :
• The nominal frequency (bFr) of the motor, if it is other than 50 Hz
• The parameters of the I/O menu, and drC menus but if the factory configuration of the speed controller
is not suitable for the application
6 - Set the following in the Set menu :
If the speed controller factory settings are not suitable :
• The acceleration (ACC) and deceleration (dEC) ramps
• The minimum (LSP) and maximum (HSP) speeds
• The motor thermal protection current (ItH)
• Other parameters as required, if the factory configuration has been changed
7 - Start the speed controller
Practical recommendations
• To help with programming the speed controller, fill in the configuration and settings tables (page 92),
in particular when the factory configuration has been changed.
• Programming the BLEMO-ER21 can be made easier by internal sequence selections and interlocks.
In order to gain the maximum benefit from this, it is recommended that the menus are accessed in the
following order :
1) - I/O 2) - drC 3) - Set
Not all steps are necessary in every case.
Caution : A check must be made to ensure that the functions which have been programmed
are compatible with the wiring layout used.