Faults - Causes - Remedies
Faults which can be reset with the automatic restart function, after the
cause has disappeared
Fault
Probable cause
Remedy
-OHF
speed controller
overload
- I
2
t too high or
- speed controller temperature too
high
- Check the motor load, the speed controller ventilation
and the environment. Wait for the controller to cool
before restarting.
-OLF
motor overload
- tripped by I
2
t motor being too high - Check the setting of the motor thermal protection,
check the motor load. Wait for the controller to cool
before restarting.
-OSF
overvoltage in
steady state or
during acceleration
- line voltage too high
- disturbed line supply
- Check the line voltage.
-USF
undervoltage
- line supply too low
- transient voltage dip
- damaged load resistor
- Check the voltage and the voltage parameter.
- Reset.
- Send the speed controller to be checked/repaired.
-ObF
overvoltage
during deceleration
- braking too sudden
or driving load
- Increase the deceleration time.
- Install a braking resistor if necessary.
- Activate the brA function if it is compatible with the
application.
-PHF
motor phase
phase failure
- speed controller incorrectly
supplied or a fuse blown
- transient phase fault
- 3-phase ER21 used on a single
phase line supply
- Check the power connection and the fuses.
- Reset
- Use a 3-phase line supply.
-OPF
motor phase
failure
- loss of a phase at the speed
controller output
- Check the connections from the speed controller to the
motor.
-SLF
serial link failure
- incorrect connection on the
speed controller connector
- Check the serial link connection on the speed
controller connector.