38
Configuration and adjustment variables
Modbus
address
CANopen
address
Code
Read/
Write
Name/Description/Possible values
64003
2262 / 4
LCC
R/WS
Control via remote display terminal
Factory setting: 0
Parameter active only with the remote display terminal option and if LAC = L1 or L2.
0 = "nO": Function inactive
1 = "YES": Enables control of the drive using the STOP/RESET, RUN and FWD/REV buttons
on the display terminal. The speed reference is then given by parameter LFr page
. Only the
freewheel, fast stop and DC injection stop commands remain active on the terminal block. If the
drive/terminal connection is cut or if the terminal has not been connected, the drive locks in an
SLF detected fault.
64002
2262 / 3
PSt
R/WS
Stop priority
WARNING
LOSS OF CONTROL
Do not set Pst to nO without external stop control.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Factory setting: 1
This function gives priority to the STOP key on the keypad or the STOP key on the remote
display terminal, regardless of the control channel (terminal block or communication bus).
0 = "nO": Function inactive
1 = "YES": STOP key priority
64001
2262 / 2
rOt
R/WS
Direction of operation authorized
Factory setting: 0
Direction of operation authorized for the RUN key.
0 = "dFr": Forward
1 = "drS": Reverse
2 = "bOt": Both directions are authorized.
9004
203C / 5
rPt
R/WS
Type of ramp
Defines the shape of the acceleration and deceleration ramps.
Factory setting: 0
0 = "LIn": Linear
1 = "S": S ramp
2 = "U": U ramp
3 = "CUS": Customized
9005
203C / 6
tA1
R/W
Start of CUS-type acceleration ramp rounded
Unit: 1% (as % of total ramp time ACC or AC2)
Factory setting: 10
Adjustment range: 0 to 100
9006
203C / 7
tA2
R/W
End of CUS-type acceleration ramp rounded
Unit: 1% (as % of total ramp time ACC or AC2)
Factory setting: 10
Adjustment range: 0 to 100 - tA1
9007
203C / 8
tA3
R/W
Start of CUS-type deceleration ramp rounded
Unit: 1% (as % of total ramp time dEC or dE2)
Factory setting: 10
Adjustment range: 0 to 100
9008
203C / 9
tA4
R/W
End of CUS-type deceleration ramp rounded
Unit: 1% (as % of total ramp time dEC or dE2)
Factory setting: 10
Adjustment range: 0 to 100 - tA3
9020
203C / 15
Inr
R/WS
Ramp increment
Factory setting: 1
0 = "0.01" : Ramp can be set between 0.05 s and 327.6 s
1 = "0.1" : Ramp can be set between 0.1 s and 3276 s
2 = "1" : Ramp can be set between 1 s and 32760 s
This parameter applies to parameters ACC, DEC, AC2 and DE2
Note: Modifying parameter Inr results in modification of the settings of parameters ACC, DEC,
AC2 and DE2.