41
Configuration and adjustment variables
(1) In corresponds to the nominal drive current indicated in the Installation Manual and on the drive rating plate.
Modbus
address
CANopen
address
Code
Read/
Write
Name/Description/Possible values
11211
2052 / C
tdC
R/W
Total DC injection braking time selected as normal stop mode
Note: This setting is not related to the "automatic standstill DC injection" function.
Unit: 0.1 s
Factory setting: 5
Adjustment range: 1 to 300
11202
2052 / 3
nSt
R/WS
Freewheel stop via logic input
Factory setting: 0
0 = "nO": Not assigned
129 = "LI1": Logic input LI1
130 = "LI2": Logic input LI2
131 = "LI3": Logic input LI3
132 = "LI4": Logic input LI4
133 = "LI5": Logic input LI5
134 = "LI6": Logic input LI6
The stop is activated when the logic state of the input is at 0. If the input falls back to state 1 and
the run command is still active, the motor will only restart if 2-wire level control has been
configured. In other cases, a new run command must be sent.
10401
204A / 2
AdC
R/W
Automatic standstill DC injection
(at the end of the ramp)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not operate on the motor during DC injection.
Failure to follow these instructions will result in death or serious injury.
Factory setting: 1
0 = "nO": No injection
1 = "YES": Standstill injection for adjustable period
2 = "Ct": Continuous standstill injection
This parameter gives rise to the injection of current even if a run command has not been
sent.
10402
204A / 3
tdC1
R/W
Automatic standstill DC injection time
Unit: 0.1 s
Factory setting: 50
Adjustment range: 1 to 300
10403
204A / 4
SdC1 R/W
Level of automatic standstill DC injection current
Unit: 0.1 A
Factory setting: 0.7 In (1)
Adjustment range: 0 to 1.2 In (1)
Note: Check that the motor will withstand this current without overheating.
10404
204A / 5
tdC2
R/W
2
nd
automatic standstill DC injection time
Unit: 0.1 s
Factory setting: 0
Adjustment range: 0 to 300
10405
204A / 6
SdC2 R/W
2
nd
level of standstill DC injection current
Unit: 0.1 A
Factory setting: 0.5 In (1)
Adjustment range: 0 to 1.2 In (1)
Note: Check that the motor will withstand this current without overheating.