35
Configuration and adjustment variables
Modbus
address
CANopen
address
Code
Read/
Write
Name/Description/Possible values
5002
2014 / 3
r2
R/WS
Relay r2
Factory setting: 0
0 = "nO": Not assigned
1 = "FLt": Drive detected fault
2 = "rUn": Drive running
4 = "FtA": Frequency threshold reached (Ftd parameter page
)
5 = "FLA": High speed (HSP) reached
6 = "CtA": Current threshold reached (Ctd parameter page
)
7 = "SrA": Frequency reference reached
8 = "tSA": Motor thermal threshold reached (ttd parameter page
9 = "bLC": Brake sequence (for information, as this assignment can be only be activated or
deactivated via the bLC parameter page
12 = "APL": Loss of 4-20 mA signal, even if LFL = nO (page
)
129 = "LI1": Returns the value of LI1.
130 = "LI2": Returns the value of LI2.
131 = "LI3": Returns the value of LI3.
132 = "LI4": Returns the value of LI4.
133 = "LI5": Returns the value of LI5.
134 = "LI6": Returns the value of LI6.
The relay is energized when the selected assignment is active, with the exception of FLt
(energized if the drive has not detected a fault).
3006
2000 / 7
LAC
R/WS
Function access level
DANGER
UNINTENDED EQUIPMENT OPERATION
• Assigning LAC to L3 will restore the factory settings of the Fr1 (below), Cd1 (page
),
), and tCC (page
) parameters.
• L3 can only be restored to L2 or L1 and L2 to L1 by means of a "factory setting" via FCS
) or by setting bit 0 of CMI to 1 (page
).
• Check that this change is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
Factory setting: 0
0 = "L1": Access to standard functions. Significantly, this level is interchangeable with ER2328.
1 = "L2": Access to advanced functions:
- +/- speed (motorized potentiometer)
- Brake control
- Switching for second current limit
- Motor switching
- Management of limit switches
2 = L3: Access to advanced functions and management of mixed control modes.
8413
2036 / E
Fr1
R/WS
Configuration reference 1
Factory setting:
1 = "AI1": Analog input AI1
2 = "AI2": Analog input AI2
3 = "AI3": Analog input AI3
16 = "AIV1": Potentiometer
If LAC = L2 or L3, the following additional assignments are possible:
160 = "UPdt": (1) + speed/- speed via LI. See configuration page
.
161 = "UpdH": (1) + speed/- speed using the jog dial. For operation, display the frequency rFr
(see page
.) The +/- speed function via jog dial is controlled from the SUP- menu by setting to
parameter rFr.
If LAC = L3, the following additional assignments are possible:
163 = "LCC": Reference via the remote display terminal, LFr parameter in the SEt- or SUP-
menu.
164 = "Mdb": Reference via Modbus
167 = "nEt": Reference via CANopen