153
[1.7 APPLICATION FUNCT.]
(FUn-)
Parameters can be accessed in
[Expert]
mode
.
(1) The parameter can also be accessed in the
[1.3 SETTINGS]
(SEt-)
menu.
Code
Name/Description
Adjustment range
Factory setting
•
[SLEEPING / WAKE UP]
(continued)
nFd
• [No Flow Period Det.]
0 to 20 min
0 min
Zero flow detection interval, in minutes.
The parameter can be accessed if
[PID feedback ass.]
(PIF)
is not
[No]
(nO).
FFd
• [NoFlo.Freq.Thres.Ac.]
(1)
0 to 500 or 1,000 Hz
according to rating
0 Hz
Zero flow detection activation threshold
The parameter can be accessed if
[PID feedback ass.]
(PIF)
is not
[No]
(nO)
and if
[No Flow Period Det.]
(nFd)
is not 0.
LFd
• [No Flow Offset]
(1)
0 to 500 or 1,000 Hz
according to rating
0 Hz
Zero flow detection offset
The parameter can be accessed if
[PID feedback ass.]
(PIF)
is not
[No]
(nO)
and if
[No Flow Period Det.]
(nFd)
is not 0.
Parameter that can be modified during operation or when stopped.