158
[1.7 APPLICATION FUNCT.]
(FUn-)
Code
Name/Description
Adjustment range
Factory setting
LLC-
•
[LINE CONTACTOR COMMAND]
LLC
• [Line contactor ass.]
[No]
(nO)
nO
LO1
-
LO4
r2
-
r4
Logic output or control relay
-
[No]
(nO)
: Function not assigned (in this case, none of the function parameters can be accessed).
-
[LO1]
(LO1)
to
[LO4]
(LO4)
: Logic output (if one or two I/O cards have been inserted, LO1 to LO2 or LO4 can be selected).
-
[R2]
(r2)
to
[R4]
(r4)
: Relay (selection of R2 extended to R3 or R4 if one or two I/O cards have been inserted).
LES
• [Drive lock]
[No]
(nO)
nO
LI1
-
-
-
-
[No]
(nO)
: Function inactive.
-
[LI1]
(LI1)
:
:
-
[...]
(...)
: See the assignment conditions on page
109
.
The drive locks when the assigned input or bit changes to 0.
LCt
• [Mains V. time out]
5 to 999 s
5 s
Monitoring time for closing of line contactor. If, once this time has elapsed, there is no voltage on the drive
power circuit, the drive will lock with an
[input contactor]
(LCF)
fault.