[1.8 FAULT MANAGEMENT]
(FLt-)
Code
Name/Description
Adjustment range
Factory setting
brP-
•
[DB RES. PROTECTION]
brO
• [DB res. protection]
[No]
(nO)
nO
YES
FLt
-
[No]
(nO)
: No braking resistor protection (thereby preventing access to the other function parameters).
-
[Alarm]
(YES)
: Alarm. The alarm may be assigned to a logic output or a relay (see page
91
).
-
[Fault]
(FLt)
: Switch to fault (bOF) with locking of drive (freewheel stop).
Note: The thermal state of the resistor can be displayed on the graphic display terminal.
It is calculated for as long as the drive control remains connected to the power supply.
brP
• [DB Resistor Power]
0.1 kW (0.13 HP) to
1,000 kW (1,333 HP)
0.1 kW (0.13 HP)
The parameter can be accessed if
[DB res. protection]
(brO)
is not
[No]
(nO)
.
Rated power of the resistor used.
brU
• [DB Resistor value]
0.1 to 200 Ohms
0.1 Ohm
The parameter can be accessed if
[DB res. protection]
(brO)
is not
[No]
(nO)
.
Rated value of the braking resistor in Ohms.
tnF-
•
[AUTO TUNING FAULT]
tnL
• [Autotune fault mgt]
[Freewheel]
(YES)
nO
YES
-
[Ignore]
(nO)
: Fault ignored.
-
[Freewheel]
(YES)
: Freewheel stop.
Parameter that can be modified during operation or when stopped.