28
Interdependence of parameter values
The configuration of certain parameters modifies the adjustment range of other parameters, in order to reduce the risk of errors. This may
result in the modification of a factory setting or a value you have already selected.
Example 1:
1.
1.
1.
1.
[Switching freq.]
(SFr)
page
72
set to 16 kHz.
2.
2.
2.
2.
[Sinus filter]
(OFI)
, see page
72
, set to
[Yes]
(YES)
(and confirmed with “ENT”) limits
[Switching freq.]
(SFr)
to 8 kHz.
If you set
[Sinus filter]
(OFI)
to
[No]
(nO)
,
[Switching freq.]
(SFr)
will no longer be limited but will remain at 8 kHz. If you require 16 kHz,
you must reset
[Switching freq.]
(SFr)
.
Example 2:
1.
1.
1.
1.
The factory setting of
[Switching freq.]
(SFr)
page
72
remains unchanged at 2.5 kHz.
2.
2.
2.
2.
Setting
[Sinus filter]
(OFI)
page
72
to
[Yes]
(YES)
(and confirming with “ENT”) changes the factory setting of
[Switching freq.]
(SFr)
to 4 kHz.
3.
3.
3.
3.
If you set
[Sinus filter]
(OFI)
to
[No]
(nO)
,
[Switching freq.]
(SFr)
will remain at 4 kHz. If you require 2.5 kHz, you must reset
[Switching freq.]
(SFr)
.