55
[1.3 SETTINGS]
(SEt-)
(1) If a graphic display terminal is not in use, values greater than 9,999 will be displayed on the 4-digit display with a period mark after the
thousand digit, e.g. 15.65 for 15,650.
Code
Name/Description
Adjustment range
Factory setting
SrP
• [+/-Speed limitation]
0 to 50%
10%
*
See page
136
Limitation of +/- speed variation
rPG
• [PID prop. gain]
0.01 to 100
1
*
See page
143
Proportional gain
rIG
• [PID integral gain]
0.01 to 100
1
*
See page
144
Integral gain
rdG
• [PID derivative gain]
0.00 to 100
0
*
See page
144
Derivative gain
PrP
• [PID ramp]
0 to 99.9 s
3.0 s
*
See page
144
PID acceleration/deceleration ramp, defined to go from
[Min PID reference]
(PIP1)
to
[Max PID reference]
(PIP2)
and vice versa.
POL
• [Min PID output]
-500 to 500 or -1,000
to 1,000 according
to rating
0 Hz
*
See page
144
Minimum value of regulator output in Hz
POH
• [Max PID output]
0 to 500 or 1,000
according to rating
60 Hz
*
See page
144
Maximum value of regulator output in Hz
PAL
• [Min fbk alarm]
See page
144
(1)
100
*
See page
144
Minimum monitoring threshold for regulator feedback
PAH
• [Max fbk alarm]
See page
144
(1)
1,000
*
See page
144
Maximum monitoring threshold for regulator feedback
*
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.