89
[1.5 INPUTS / OUTPUTS CFG]
(I-O-)
The encoder configuration can also be accessed in the
[1.4 MOTOR CONTROL]
(drC-)
menu.
Code
Name/Description
Adjustment range
Factory setting
IEn-
•
[ENCODER CONFIGURATION]
The encoder parameters can only be accessed if the encoder card has been inserted, and the available
selections will depend on the type of encoder card used.
EnS
• [Encoder type]
[AABB]
(AAbb)
nO
AAbb
Ab
A
The parameter can be accessed if an encoder card has been inserted.
To be configured in accordance with the type of encoder used.
-
[----]
(nO)
: Card missing.
-
[AABB]
(AAbb)
: For signals A, A-, B, B-.
-
[AB]
(Ab)
: For signals A, B.
-
[A]
(A)
: For signal A. Value cannot be accessed if
[Encoder usage]
(EnU)
page
90
=
[Spd fdk reg.]
(rEG)
.
EnC
• [Encoder check]
[Not done]
(nO)
nO
YES
dOnE
Encoder feedback check See procedure page
71
.
The parameter can be accessed if an encoder card has been inserted and if
[Encoder usage]
(EnU)
page
90
is not
[Speed ref.]
(PGr)
.
-
[Not done]
(nO)
Check not performed.
-
[Yes]
(YES)
: Activates monitoring of the encoder.
-
[Done]
(dOnE)
: Check performed successfully.
The check procedure checks:
- The direction of rotation of the encoder/motor
- The presence of signals (wiring continuity)
- The number of pulses/revolution
If a fault is detected, the drive locks in
[Encoder fault]
(EnF)
fault mode.