PKP2500SI_CANopenUM_REV1.0
20/38
24.
Object 2014h: Set startup LED show
Set message:
Identifier
600h + current CAN ID
Default 615h
Byte 0
2Fh
Set Device Register
Byte 1
14h
CAN Object 2014h
Byte 2
20h
Byte 3
00h
Sub index
Byte 4
XXh
00h: Disable
01h: Complete LED Show (default)
02h: Fast Flash
Byte 5,7
00h
Not used
Read message:
Identifier
600h + current CAN ID
Default 615h
Byte 0
40h
Read Device Register
Byte 1
14h
CAN Object 2014h
Byte 2
20h
Byte 3
00h
Sub index
Byte 4,7
00h
Not used
Example:
Direction
Identifier
Format
Message
Data
To Keypad
615
Std
2F 14 20 00 00 00 00 00
Startup LED show disabled
Keypad reply
595
Std
60 14 20 00 00 00 00 00
Command accepted
To Keypad
615
Std
40 14 20 00 00 00 00 00
Read command set
Keypad reply
595
Std
4F 14 20 00 00 00 00 00
Startup LED show disabled