background image

Manual 

EB-MODBUS-RTU 

 

 

BLOCK Transformatoren-Elektronik GmbH 

 

 

Max-Planck-Straße 36-46 27283 

Verden, Germany 

10-23-17 / KRUT 

Subject to technical changes 

 

Page: 11

 

 

6.2.

 

EB Single Channel Circuit Breaker  

 

Table 2: 

Register overview for EB-0824-100-0, EB-1824-xxx-0 and EB-3824-100-0

 

  

  

Query 

Response 

Function 

Circuit Breakers 

Starting Address 

Value 

Description 

Query status output OK

 

  

1  -  40 

101  -  140 

  

  

READ_COIL_Status

  1 

        

        

  Off 

     

        

        

  On 

Query status only

 

  

1     40 

201  -  240 

  

  

READ_HOLDING_REGISTERS  3 

        

        

high byte

 

see EB status byte

 

Query actual current 

  

1     40 

301  -  340 

  

  

READ_HOLDING_REGISTERS  3 

        

        

high byte

  in mA  

     

        

        

low byte

  in mA  

Query nominal current 

  

1  -  40 

401  -  440 

  

  

READ_HOLDING_REGISTERS  3 

        

        

high byte

  in mA  

     

        

        

low byte

  in mA  

Query combination status

 

  

1  -  40 

501  -  540 

  

  

READ_HOLDING_REGISTERS  3 

        

        

1. byte 

Status of EB-MODBUS-RTU signaling contacts 

    

        

        

0x00 

No events

 

    

        

        

0x01 

Signal contact 14 (off / tripped)

 

    

        

        

0x02 

Signal contact 24 (nominal current> = 90%)

 

    

        

        

  

 

    

        

        

2. byte 

EB circuit breaker status 

    

        

        

  

See EB status byte

 

    

        

        

    

    

        

        

3-4. byte 

EB circuit breaker actual current 

    

        

        

high byte

  in mA  

    

        

        

low byte

  in mA  

    

        

        

  

 

    

        

        

5-6. byte 

EB circuit breaker nominal current 

    

        

        

high byte

  in mA  

    

        

        

low byte

  in mA  

    

        

        

  

 

    

        

        

7-8. byte 

EB-MODBUS-RTU Power Supply 

    

        

        

high byte

  in mV 

    

        

        

low byte

  in mV 

     

        

        

     

Query device ID

 

  

1  -  40 

601  -  640 

  

  

READ_HOLDING_REGISTERS  3 

        

        

1-

2. byte

 

Firmware version

 

    

        

        

3-

6. byte

  Production order 

    

        

        

7-

10. byte

 

Serial number

 

    

        

        

11-

12. byte

 

Variant (see

 

EB variants)

 

Query options

 

  

1  -  40 

701  -  740 

  

  

READ_HOLDING_REGISTERS  3 

        

        

high byte

 

Options (see Options)

 

    

        

        

low byte

 

Options (see Options)

 

    

        

        

high byte

 

Options Complement (see Options)

 

     

        

        

low byte

 

Options Complement (see Options)

 

Set status

 

  

1  -  40 

501  -  540 

    

WRITE_SINGLE_REGISTER  6 

        

        

0x01  Off 

    

        

        

0x02  On 

    

        

        

0x04 

Reset

 

Set status

 

  

All 

500 

  

For all devices in the network   

WRITE_SINGLE_REGISTER  6 

        

        

0x01  Off 

    

        

        

0x02  On 

    

        

        

0x04 

Reset

 

Set nominal current 

  

1  -  40 

401  -  440 

  

  

WRITE_SINGLE_REGISTER  6 

        

        

high byte

  Nominal current in mA  

     

        

        

low byte

  Nominal current in mA  

Set options

 

  

1  -  40 

701  -  740 

  

Only for one device

 

WRITE_MULTIPLE_REGISTERS  16 

        

        

high byte

 

Options (see Options)

 

    

        

        

low byte

 

Options (see Options)

 

    

        

        

high byte

 

Options Complement (see Options)

 

     

        

        

low byte

 

Options Complement (see Options)

 

Summary of Contents for EB-MODBUS-RTU

Page 1: ...ck Straße 36 46 27283 Verden Germany 10 23 17 KRUT Subject to technical changes Page 0 EB MODBUS RTU Communication Module Between PLC PC and EasyB Single Channel Circuit Breaker System Collective Reset Input 2 Potential Free Collective Signaling RS 485 RS 422 Interface ...

Page 2: ...ch 3 2 3 Terminals 4 3 Initialization 4 4 Configuration 5 4 1 Dip switch 5 4 2 Byte Information 6 4 3 Configuration Example 2 Wire 6 4 4 Configuration Example 4 Wire 7 5 Communication and Examples 8 5 1 Loopback Diagnostic Test 8 5 2 Status Check 8 5 3 Error Message 9 6 Register Overview 10 6 1 EB MODBUS RTU 10 6 2 EB Single Channel Circuit Breaker 11 6 3 EB Status Byte 12 6 4 Coding of the Circui...

Page 3: ...respective task in particular the safety instructions and warnings contained therein Qualified personnel can as a result of their training and experience help to ensure that the use of the described product meets all safety requirements as well as applicable regulations provisions standards and laws 1 3 Intended Use This device is designed for installation within an enclosure and is suitable for u...

Page 4: ...ption of the Communication Module The EB MODBUS RTU communication module serves as an interface for connection to a higher level controller and is compatible with circuit breakers of the variants EB 08 EB 18 and EB 38 To ensure error free operation the maximum number of 40 circuit breakers must not be exceeded 2 2 Functional Sketch Note Deviations in the wiring can destroy the modules ...

Page 5: ...iguration must be made The MODBUS module initializes itself by applying the supply voltage to terminal IN Functional operation is only made possible by connecting circuit breaker modules and then applying the supply voltage to IN After the supply voltage has been applied all connected circuit breakers are addressed one after the other and then selectively switched on one after the other Using the ...

Page 6: ...re Connection Send 2 4 wire End of frame time 1 2 3 4 5 6 7 8 0 0 3 5 Byte 0 1 10 ms 1 0 50 ms 1 1 500 ms 1 2 3 4 5 6 7 8 0 0 0 0 Term PullUp off 1 1 0 0 RS485 Term PullUp Dn 1 1 1 1 RS422 Term PullUp Dn ModBus address 1 2 3 4 5 6 7 8 0 0 0 0 1 ModBus addr 1 x x x x x ModBus addr X 1 1 1 1 1 ModBus addr 31 Baud rate 1 2 3 4 5 6 7 8 0 0 9600 Bd 0 1 4800 Bd 1 0 19200 Bd 1 1 38400 Bd Parity stop bits...

Page 7: ...Page 6 4 2 Byte Information 1 Start bit The information byte consists of 8 Information bits 2 stop bits without parity bit or 1 stop parity bit even 4 3 Configuration Example 2 Wire 2 wire send receive EOF 10 ms ModBus addr 1 19200 Bd 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 1 0 0 1 0 0 1 0 0 0 0 1 0 1 0 Slave EB MODBUS RTU Rx Rx Tx Tx Rx Master Tx Tx Rx ...

Page 8: ... 36 46 27283 Verden Germany 10 23 17 KRUT Subject to technical changes Page 7 4 4 Configuration Example 4 Wire 2 wire send receive EOF 10 ms ModBus addr 1 19200 Bd 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 1 1 1 0 1 0 1 0 0 0 0 1 0 1 0 Slave EB MODBUS RTU Rx Rx Tx Tx Rx Master Tx Tx Rx ...

Page 9: ...S Addr Function CRC L CRC H Telegram Slave Master 1 8 0 0 AA 55 5E 94 5 2 Status Check Interrogate circuit breaker 1 via EB MODBUS RTU MODBUS DATA MODBUS Addr Function r w Start Addr Number of States CRC Telegram Master Slave Byte Byte h byte l byte h byte l byte l byte h byte 1 1 1 245 0 1 150 122 CRC Number of selected circuit breakers devices register addresses always 1 Circuit breaker 1 status...

Page 10: ... Germany 10 23 17 KRUT Subject to technical changes Page 9 5 3 Error Message Addr Function Data Description X Func 0x80 1 Use of an unsupported short code 2 Use of an unauthorized memory register 3 Wrong value 6 Device cannot process request at the moment Repeat request later 8 Field is read only ...

Page 11: ...f 0x01 Switched on current above warning threshold 90 nominal current Query device ID 4 READ_HOLDING_REGISTERS 3 1 2 byte Firmware version 3 6 byte Production order 7 10 byte Serial number 11 12 byte Variant see EB variants Query options 5 READ_HOLDING_REGISTERS 3 high byte Options see Options low byte Options see Options high byte Options Complement see Options low byte Options Complement see Opt...

Page 12: ...atus See EB status byte 3 4 byte EB circuit breaker actual current high byte in mA low byte in mA 5 6 byte EB circuit breaker nominal current high byte in mA low byte in mA 7 8 byte EB MODBUS RTU Power Supply high byte in mV low byte in mV Query device ID 1 40 601 640 READ_HOLDING_REGISTERS 3 1 2 byte Firmware version 3 6 byte Production order 7 10 byte Serial number 11 12 byte Variant see EB vari...

Page 13: ...tched on current above warning threshold 90 nominal current flashes E Switched on current above warning threshold 100 nominal current flashes R off hardware error fuse flashes V off thermal release flashes E off locally by key as of circuit breaker version 1 12 lights up RC rotary wheel position Note If a circuit breaker was switched off locally it can only be switched back on locally This functio...

Page 14: ...0 Tripping current 10 A 6 5 EB Variants Coding of the options registers 601 640 is shown in Table 2 Table 5 Coding of the Types Name Value Description EB MODBUS RTU 0xCC10 MODBUS RTU Communication Module EB IO LINK 0xCC20 IO LINK Communication Module EB 3824 100 0 0xCBAA Tripping currents can only be set via the interface 0 5 10A EB 0824 100 0 0xCB8A Tripping currents adjustable via interface or a...

Page 15: ... 1 0 Meaning 1 1 Switched off or signaled as tripped 0 Signal as tripped only 2 1 OK signal inverted 0 Do not invert OK signal 3 1 Switch Automatic Addressing off 0 Switch Automatic Addressing on Note The circuit breaker options correspond to delivery condition 3 dec i e the first two options are set The Automatic Addressing on off option is only available with protection switch version 1 10 and e...

Page 16: ... reset Switched off or signaled as tripped Bit No 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Options 1 set activate only the rest remain unchanged Options Complement 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 reset Invert OK signal Bit No 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Options 1 set activate only the rest remain unchanged Options Complement 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 reset Activate Invert OK signal Ac...

Reviews: