BATTERY TEMPERATURE SENSOR

 

 

 

 

Installation of the optional battery temperature sensor enables temperature compensation of all charge voltage setpoints. In a multi-controller system a 

single temperature sensor must connect to the IPN master. Do not attach a sensor or connections other than Blue Sky Energy battery temperature sensor p/n 
930-0022-20. The cable may be lengthened or shortened if necessary. Be certain to observe proper RED/BLK polarity. 

 

BATTERY AND PV WIRING 

 

 

A desirable installation will produce a total system wiring voltage drop of 3% or less. The lengths shown in Table 2 are one way from the PV modules to the 

battery with the 1524 located along the path. Wire length can be increased inversely proportional to actual current. If current was reduced by ½, wire lengths could 
be doubled and still provide the same 3% voltage drop. 

 

¾

 

CAUTION:

 Battery, PV and Auxiliary Output terminal block accept #20

10 AWG wire and are to be tightened to 9 in-lb (1 

nm). IPN Network and Temperature Sensor compression terminals accept #24

14 AWG wire and are to be tightened to 2.1 in-

lb (0.24 nm). DO NOT connect Bat– and PV– together outside of the unit or improper operation will result. Bat– and PV– connect 
together internally. 

 

MAXIMUM CONDUCTOR PAIR LENGTH   -   3% VOLTAGE DROP 

 

WIRE GAUGE 

AWG 

12 VOLT SYSTEM @16A 

FEET / METERS 

24 VOLT SYSTEM @12A 

FEET / METERS 

12 AWG 

8.0 / 2.4 

21.4 / 6.6 

10 AWG 

12.8 / 4.0 

33.8 / 10.4 

8 AWG 

20.2 / 6.2 

53.8 / 16.4 

6 AWG 

32.4 / 9.8 

85.6 / 26.0 

4 AWG 

51.0 / 15.6 

136.2 / 41.4 

 

TABLE 2 

 

SETUP AND WIRING DIAGRAM 

 

 

FIGURE 3 

 

AUXILIARY OUTPUT 

 

 

The auxiliary output can serve one of three functions; a 2 amp auxiliary battery charger, a 20 amp 12V or 15 amp 24V load controller with Low Voltage 

Disconnect (LVD), or a 15/20 amp variable Dusk-to-Dawn lighting controller. The Charge/Load function is selected by DIP switch #3 shown in Figure 3. The IPN-
ProRemote is required to adjust LVD thresholds or enable Dusk-to-Dawn lighting control. Auxiliary outputs in a networked multi-controller system will function 
normally, but only the auxiliary output in the master can be configured or monitored using the IPN-ProRemote. The auxiliary output Load Indicator will illuminate 
whenever the auxiliary output is ON. 

 

¾

 

CAUTION:

 The auxiliary output cannot perform both auxiliary battery charge and load control functions at the same time. Do not 

connect to the Load+ terminal for auxiliary battery charge. 

 

 

 

 

 

Summary of Contents for SOLAR BOOST 1524iX

Page 1: ...ING PHOTOVOLTAIC CHARGE CONTROLLER INSTALLATION AND OPERATION MANUAL THIS MANUAL INCLUDES IMPORTANT SAFETY INSTRUCTIONS FOR MODEL SB1524iX SAVE THESE INSTRUCTIONS COVERED UNDER ONE OR MORE OF THE FOLLOWING US PATENTS 6 111 391 6 204 645 Blue Sky Energy Inc 2011 430 0029 B ...

Page 2: ...rk 5 INSTALLATION 5 Electrostatic Handling Precautions 6 Battery and PV Voltage 6 Selecting PV Modules 6 As Shipped Factory Default Settings 6 Equalize Enable 6 Battery Temperature Sensor 6 Battery and PV Wiring 7 Auxiliary Output 7 Auxiliary Battery Charge 8 Load Controller 8 Dusk to Dawn Lighting Control 8 Installing a Multi Controller System 8 IPN Network Address 9 Mounting 9 TROUBLESHOOTING GU...

Page 3: ...ng a severe burn j Remove all sources of power photovoltaic and battery before servicing or installing 4 CHARGER LOCATION INSTALLATION a This unit is designed to charge 12V 6 cell or 24V 12 cell flooded or sealed type lead acid chemistry batteries within the range of 10 to 5 000 amp hours Follow battery manufacturers charging recommendations when considering this unit for use with other battery ch...

Page 4: ...displays If net battery charge current is greater than 3 to 5 amps per 100 amp hours of battery capacity the charge status indicator can provide a rough indication of battery state of charge CHARGE STATUS INDICATOR CHARGE STATUS INDICATOR CHARGE MODE APPROXIMATE CHARGE LEVEL OFF CHARGE OFF CONTINUOUSLY ON BULK 70 FULL BLINKING 1 SEC ON 1 SEC OFF ACCEPTANCE 70 95 FULL BLINKING 0 2 SEC ON 1 SEC OFF ...

Page 5: ... SB1524 can perform automatic equalization alone or manual equalization via the IPN ProRemote Equalization is essentially a controlled overcharge which applies a relatively high voltage to bring all battery cells up to the same specific gravity and eliminates electrolyte stratification by heavily gassing the battery While equalization parameters are adjustable with the IPN ProRemote factory defaul...

Page 6: ...n the unit is operating at high power When mounted vertically as described in the installation section the unit can deliver full output in an ambient temperature of up to 50 C 122 F If an over temperature condition exists the unit will shut down and the Charge Status Indicator will display an OFF condition The 1524 does not include a digital type temperature sensor and will always show the heatsin...

Page 7: ...e very different consider using a separate charge controller for each module type to obtain the best MPPT current boost performance Select PV modules that do not exceed the maximum ratings shown below and preferably produce at least 3A of IMP per 100 amp hours of battery capacity Recommended range of VMP at STC Nominal Battery Voltage Automatic Current Limit Maximum PV Power STC Maximum PV Isc STC...

Page 8: ...to 2 1 in lb 0 24 nm DO NOT connect Bat and PV together outside of the unit or improper operation will result Bat and PV connect together internally MAXIMUM CONDUCTOR PAIR LENGTH 3 VOLTAGE DROP WIRE GAUGE AWG 12 VOLT SYSTEM 16A FEET METERS 24 VOLT SYSTEM 12A FEET METERS 12 AWG 8 0 2 4 21 4 6 6 10 AWG 12 8 4 0 33 8 10 4 8 AWG 20 2 6 2 53 8 16 4 6 AWG 32 4 9 8 85 6 26 0 4 AWG 51 0 15 6 136 2 41 4 TA...

Page 9: ...d to setup and enable lighting control Refer to IPN ProRemote operators manual for lighting control setup instructions Variable time settings are available to turn lighting ON after Dusk Post Dusk timer and or ON before Dawn Pre Dawn timer If both timers are set to DISABLED factory default the lighting control feature is disabled If either the Post Dusk or Pre Dawn timers are set to a time value t...

Page 10: ...roller must be set to address 0 zero to serve as the master The other controllers must be set to address 1 7 with no two controllers set the same The 1524 requires that a jumper be soldered across location A2 to select addresses 4 through 7 IPN NETWORK ADDRESS MASTER SLAVES DIP SWITCH 0 1 2 3 4 5 6 7 JUMPER A2 NO NO NO NO YES YES YES YES 1 A1 OFF OFF ON ON OFF OFF ON ON 2 A0 OFF ON OFF ON OFF ON O...

Page 11: ... charged and battery voltage is high Output during MPPT operation is constant power higher battery voltage reduces charge current increase VMP and available power decrease with increasing PV cell temperature Cooler PV s will produce greater boost It is normal for boost to decrease as PV temperature rises Replace use as is or use different controller for different PV modules Auxiliary battery not b...

Page 12: ... Energy Inc hereinafter BSE hereby warrants to the original consumer purchaser that the product or any part thereof shall be free from defects due to defective workmanship or materials for a period of five 5 years subject to the conditions set forth below 1 This limited warranty is extended to the original consumer purchaser of the product and is not extended to any other party 2 The limited warra...

Reviews: