507270-03B
Page 19 of 58
Issue 1904
BG921UH Maximum Allowable Intake or Exhaust Vent Length in Feet
Standard Termination at Elevation 0 - 10,000 ft
Number of 90°
Elbows Used
2" Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
045
070
090
045
070
090
045
070
090
1
76
61
39
110
95
63
132
132
113
2
71
56
34
105
90
58
127
127
108
3
66
51
29
100
85
53
122
122
103
4
61
46
24
95
80
48
117
117
98
5
56
41
19
90
75
43
112
112
93
6
51
36
14
85
70
38
107
107
88
7
46
31
9
80
65
33
102
102
83
8
41
26
n/a
75
60
28
97
97
78
9
36
21
70
55
23
92
92
73
10
31
16
65
50
18
87
87
68
Concentric Termination Elevation 0 - 10,000 ft
Number of 90°
Elbows Used
2" Pipe
2-1/2" Pipe
3" Pipe
Capacity
Capacity
Capacity
045
070
090
045
070
090
045
070
090
1
68
53
37
100
85
59
116
116
109
2
63
48
32
95
80
54
111
111
104
3
58
43
27
90
75
49
106
106
99
4
53
38
22
85
70
44
101
101
94
5
48
33
17
80
65
39
96
96
89
6
43
28
12
75
60
34
91
91
84
7
38
23
7
70
55
29
86
86
79
8
33
18
n/a
65
50
24
81
81
74
9
28
13
60
45
19
76
76
69
10
23
8
55
40
14
71
71
64
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and
Exhaust must be same pipe size.
Table 5A.
Summary of Contents for BG921UH
Page 3: ...507270 03B Page 3 of 58 Issue 1904 Parts Arrangement Figure 1 ...
Page 24: ...507270 03B Page 24 of 58 Issue 1904 Figure 25 Figure 26 ...
Page 38: ...507270 03B Page 38 of 58 Issue 1904 Figure 58 Trap Drain Assembly Using 1 2 PVC or 3 4 PVC ...
Page 44: ...507270 03B Page 44 of 58 Issue 1904 Figure 67 Typical Wiring Diagram ...