background image

 

- 11 - 

POSITIONING   

POSITIONING 

 

A rolling lift jack, air sled, or pallet jack should be used for positioning the unit. Do not push against the edges or sides of the unit in 
an attempt to slide it into position. Although all metal parts are deburred during manufacture, serious injury could occur if the unit 

were to move suddenly while being positioned by hand.  We recommend you use gloves during installation process.  Do not use the 
oven door handle as a “pull.” Pushing or pulling the unit increases the possibility of damage to the legs and floor.

 

LEVELING 

 

For optimum performance, (particularly in baking), the range must be leveled by the leveling bullet legs installed in the range by 
screwing the bullet in or out. 

 
A carpenter-type level should be placed on the oven rack, and the unit should be leveled side-to-side, front-to-back, and diagonally. 

NOTE:  

Installing this range on a combustible surface without legs will void UL/cUL classification.

 

 

 

GAS CONNECTION 

 

The gas supply line must be the same size or larger than the gas inlet on the unit. This unit has a ½” or ¾” NPT inlet accessed from the 

back of the unit.  We recommend the gas inlet should be approximately ¼ “ larger than the NPT inlet (see page 12 for more 
information).  Sealants used on all pipe joints must be resistant to LP gas.  Any openings in the wall behind the unit, or the floor 

beneath must be sealed. 
1. An installer-provided manual shut-off valve must be installed in the gas service line ahead of the appliance.  The shut-off valve must 

be in a position where it can be accessed quickly in the event of an emergency. 
2. All heavy-duty cooking equipment must have a pressure regulator on the incoming service line for safe and efficient operation. 

Service pressure may fluctuate due to local demand. An external regulator is not required on the unit, as a regulator is built in to each 
unit at the factory. Under no condition should the factory-installed regulator be by-passed. 
 This unit was constructed for use with either natural or propane (LP) gas. Verify that the unit and the incoming gas supply are 
compatible by checking the rating plate label, located on the left side of the unit under the burner grate. The correct regulator, valves, 

and orifices are installed at the factory for natural/LP gas. See the following section, titled "GAS CONVERSION," for detailed 
conversion instructions, if required. 
  Incoming line pressure should be checked with a manometer. The correct operating manifold pressure for natural gas is 5.0" WC; for 
Propane (LP) gas, 10.0" WC.  Incoming line pressure upstream of the regulator should be 1" WC higher than the correct operating 

manifold pressure. The regulator used on this unit will withstand a maximum input pressure of 1/2 psi, (12" WC). If the incoming line 
pressure is higher than this maximum rating, a step-down regulator is required upstream of the unit's factory-installed regulator. 
  The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of 
the homes’ gas line system at pressures in excess of 1/2 psig, (3.5kPa). 
 The appliance must be isolated from the gas supply piping system by closing its individual shut-off valve during any testing of the 
homes’ gas system at pressures equal to or less than 1/2 psig, (3.5kPa). 
3. Rigid connections:  Incoming gas is brought from the inlet pipe at the rear of the unit to the pressure regulator, then through the 
upper manifold for distribution. The only connection necessary is from the service line, through the installer-supplied shut-off valve, to 

this inlet pipe. 
  Be sure to double check any installer-supplied pipes and fittings, and/or blow compressed air through them to clean out dirt particles, 

threading chips, or other foreign matter before connecting the unit to the service line. Such particles will clog orifices when gas pressure 
is applied. 

Service to clean such clogs is not covered by the warranty.

 

 Check all gas connections for leaks using a soapy solution before lighting any pilots. 

DO NOT USE AN OPEN FLAME TO 

CHECK FOR LEAKS! 

Using an open flame to check a new connection is not only dangerous, but it will also miss small leaks that a 

soapy solution would detect. 
4. Flexible connections:  If the unit is to be installed with flexible couplings and/or a "quick-disconnect," the installer must use a 

commercially approved AGA Design Certified flexible connector of at least 1/2" NPT, in compliance with ANSI Z21.41.  
 In Canada, a connector complying with CAN 16.10 - 88, and a quick disconnect device complying with CAN 16.19M - 79 must be 

installed with a strain relief device to guard against the transmission of strain to the connector. 
5. Air shutter adjustments are the responsibility of the installer, not service. 

Summary of Contents for RNB 30

Page 1: ...RANGES COOKTOPS FOR THE HOME MODELS RNB 30 RPB 30 RGTNB 30 RNB 36 RPB 36 RGTNB 36 RNB 48 RGTNB 48 RNB 60 RGTNB 60 RCS 30 and RCS 36 Service Manual Free Standing Gas Range 600 Arlington Street Reading...

Page 2: ...nd meet and exceed our customer s expectations before during and after the service requirements that are performed on this quality product Our parts and service department has gone through great detai...

Page 3: ...Adjustment 23 Bake Broil Thermostat Replacement 24 Convection Fan Removal 25 Oven Gasket Removal 26 Door Panel Removal 27 Complete Door Removal 27 Indicator Light Removal 28 Oven Light Switch Removal...

Page 4: ...01050 02 Last two digits of year 2002 01 Month January 1 February 2 etc 50 the unit number for that months production LOCATION NOTE All Warranty Serial Plates are located on the top left inner side of...

Page 5: ...for proper installation providing normal care and maintenance and proof of purchase and delivery date upon request as well as making the appliance accessible for service Warrantor s liability on a cl...

Page 6: ...The installation of this appliance must conform with local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z223 1 In Canada installation must be in accordance with the cur...

Page 7: ...e from the unit to such combustible surfaces must be maintained 18 above the counter height 3 Wall Cabinets Wall cabinets to the side s of the shelf flue riser must be a minimum of 18 above the counte...

Page 8: ...8 RANGETOP CUTOUT AND SPECIFICATIONS Unit Size Cutout Width 30 30 36 36 48 48 60 60 Depth 24 Height 7 Lower Support Ledge 1 Maximum...

Page 9: ...ot refuse delivery but contact the carrier and file the appropriate freight claims Do not contact the factory as responsibility for shipping lies with the carrier dealer and end user We will assist wi...

Page 10: ...used without the 6 clearance recommended a non combustible rear wall extending a minimum of 6 below the countertop must be used In no cases will we accept responsibility for claims which may result f...

Page 11: ...e the following section titled GAS CONVERSION for detailed conversion instructions if required Incoming line pressure should be checked with a manometer The correct operating manifold pressure for nat...

Page 12: ...CE SIZE L P ORIFICE SIZE LISTED BTU P H ACTUAL BTU P H FIXED OR ADJUSTABLE PRESSURE REG NAT LP CHARBROILER BURNER U 51 P N 709551 57 P N 709557 20 000 15 400 14 500 ADJ REG P N 718301 REQD ON ALL MODE...

Page 13: ...13 WCI to the manifold WCI Water Column Inches...

Page 14: ...east this gauge NOTE If electrical power is not supplied or is interrupted the unit will not be operational WARNING This appliance is equipped with a three pronged grounded plug for your protection ag...

Page 15: ..._ 4 Check gas pressure at the manifold remove a burner install tube from a manometer onto the orifice without burner on it Ignite burners on top section during test to equalize pressure in the manifol...

Page 16: ...to document data Temperature Conventional Oven 350 degrees Cycle 1 2 3 4 5 Average High XXXX XXXX Low XXXX XXXX Temperature Convection Oven 325 degrees Cycle 1 2 3 4 5 Average High XXXX XXXX Low XXXX...

Page 17: ...valve Small Oven 156901 Gas valve Dual Simmer Valve Assy 718301 Pressure Regulator Front Accessibility indicates that the range does not need to be removed from the installed location but will requir...

Page 18: ...Grates Ring Grates Reignition Spark Module Control Panel RPB RPBGT Thermostat Griddle Griddle Plate Pull wires forward Control Panel Manifold Gas Valves all Control Panel Valve Switches Control Panel...

Page 19: ...nect the wires from the switch light and fan carefully marking the location of the wires in order to rewire the switches positioned in the new control panel or to simply replace wires in the correct l...

Page 20: ...f with the thermostat cycling contacts The igniter can be checked for continuity by using an ohmmeter set to the Rx10 range Remove the igniter from the burner and disconnect the igniter wiring Attach...

Page 21: ...21...

Page 22: ...r the lower kick panel and remove completely from the Product 5 Locate the 2 wire nuts tying the igniter to the power supply and remove This will allow you to pull the old igniter through to the oven...

Page 23: ...ity Please note If the range that you are performing service on does not allow the wires to come through to the oven cavity from the front the range must be pulled away from the wall This will then al...

Page 24: ...amperage reading less than 3 2 will cause the gas valve to partially open resulting is a reduced gas flow to burners A continuity test can be made to check the bi metal arm heater by using an ohmmeter...

Page 25: ...er securing screws positioned at the lower outside edge of the inner kick panel 2 Utilizing a straight stubby screwdriver or a 3 16 open end box wrench loose the screw which is securing the air shutte...

Page 26: ...he left front and rear top grates from the range to gain access to the capillary tube wire which is routed through the left side of the burner box bottom 7 Gently guide the capillary bulb through the...

Page 27: ...the motor assembly to the front through the motor opening in the back cavity 6 Disconnect the wires on the motor assuring the location in order to reconnect the new motor to the wire leads 7 Reconnec...

Page 28: ...rame of the range The gasket is snapped into the front frame holes by tiny wire clips Take caution in reinstalling new gasket so not bend or break the wire clips during reinstallation 4 Close door ass...

Page 29: ...door completely 2 At the top of each hinge immediately next to the frame there is a clip that rotates out The clip is easy to open using a screwdriver Place the tip of the screwdriver in the square op...

Page 30: ...g screws located in the upper flange located underneath the plate rail and the screws located on the lower flange located above the pull out grease pan handles 3 Disconnect the wiring from the existin...

Page 31: ...a continuity tester 4 Disconnect the wires from the switch and attach the meter or tester leads to the switch terminals Continuity or low ohms should be indicated when the switch contacts are closed a...

Page 32: ...changed 5 Utilizing a small stubby screwdriver remove the 4 screws that hold the venturi bracket onto the venturi tube In doing so the flexible tubing being used on the range allows the orifice assem...

Page 33: ...motion is required to remove the front and rear burners b Griddle Burner Igniter Removal of an igniter wire is not required to remove griddle char broiler burner from the griddle char broiler box Alth...

Page 34: ...ection area onto the product Please Note Opening the air shutter gap will eliminate the yellow tipping on the burner Closing the air shutter gap will prevent a noisy flame that lifts off the burner po...

Page 35: ...el Removal Instructions 12 Once control panel is removed trace the other wire which will lead to the thermostat Detach wire marking its location 13 Remove igniter 14 Replace igniter rerun wire and rec...

Page 36: ...heater a Check thermostat contacts for continuity or check for 120VAC at thermostat contact BR to neutral If no voltage is present or open contacts indicated replace the thermostat If voltage is prese...

Page 37: ...Valve switch e Defective spark module f Gap too large between burner and electrode a Check power source b Replace spark electrode c Check connection between spark electrode and spark module d Check co...

Page 38: ...uniform gas pressure 1 Check gas pressure Supply Regulator 2 Check orifice for blockage Metal shavings Dirt dust Excess grease from burner valve Floating flame lazy appearance and no well defined inn...

Page 39: ...39...

Page 40: ...40...

Page 41: ...41...

Page 42: ...42...

Page 43: ...43...

Page 44: ...44...

Page 45: ...45...

Page 46: ...46...

Page 47: ...onnection Exterior Plate Rail Control Panel Oven Door Kick Panel Voltage see pg 5 Oven Interior Porcelain Finish Oven Racks Ground see pg 5 Top Section Top Grates Ring Grates Burners Polarization see...

Reviews: