25
alarm will be generated. If the UPS is turned on, it will transfer to battery mode. When neutral line
is restored and detected, the alarm will be muted automatically and the UPS will go back to normal
mode automatically.
Check:
The UPS will automatically detect the neutral loss. If neutral loss is detected, an alarm will
be generated. If the UPS is turned on, it will transfer to battery mode. When neutral is restored, the
alarm will NOT be muted automatically and the UPS will NOT go back to normal mode
automatically.
ISO Compensation
:
When UPS is connected to output isolation, it will compensate the output voltage.
Electronic Setting Page 2
Bypass UPS off
: Select the bypass status when manually turning off the UPS. This setting is only
available when “Bypass forbid.” is set to “Disable”.
Enable
: Bypass enabled. When selected, bypass mode is activated.
Disable
: Bypass disabled. When selected, no output through bypass when manually turning off
the UPS. To protect power continuity on output load, when UPS fault or UPS transfers to bypass
due to overload on AC mode, the UPS will force to turn on bypass output by default.
Bypass VOL Range
: Set the bypass voltage range.
L
: Low voltage point for bypass. The setting range is 176V ~ 209V when UPS is HV system.
The setting range is 96V ~ 110V when UPS is LV system.
H
: High voltage point for bypass. The setting range is 231V ~ 264V when UPS is HV system.
The setting range is 130V ~ 146V when UPS is LV system.
Bypass FRE Range
: Set the bypass frequency range.
The acceptable bypass frequency range from 46Hz to 54Hz when UPS is 50Hz system and from 56Hz to
64Hz when UPS is 60Hz system.
ECO mode
: Enable/Disable ECO mode. Default setting is “Disable”.
ECO VOL Range
: Set the ECO voltage range.
L:
Low voltage point for ECO mode. The setting range is from “Rated output voltage – 5V” to
“Rated output voltage - 11V”. “Rated output voltage – 5V” is default setting.
H:
High voltage point for ECO mode. The setting range is from “Rated output v 5V” to
“Rated output v 11V”. “Rated output v 5V” is default setting.
ECO FRE Range
: Set the ECO frequency range. The setting range is from 46Hz to 54Hz when the UPS
is 50Hz system and from 56Hz to 64Hz when the UPS is 60Hz system.
BATTERY