26
Battery setting page
BATT Warning VOL
: Set battery warning voltage.
HIGH
: High battery warning voltage. The setting range is 14.0V ~ 15.0V. 14.4V is default setting.
LOW
: Low battery warning voltage. The setting range is 10.1V ~ 14.0V. 11.4V is default setting.
This parameter setting is related to “Shutdown Voltage” setting. This setting value should be
higher than “Shutdown Voltage” setting.
Shutdown VOL
: If battery voltage is lower than this point in battery mode, UPS will automatically shut
down. The setting range is 10.5V ~ 12.0V. 10.7V is default setting.
BATT Age:
Set up battery age.
Battery Parameters
:
Battery AH: setting battery capacity.
MISCELLANEOUS
Miscellaneous setting page
Auto Restart
:
Enable
: After “Enable” is set, once UPS shutdown occurs due to low battery and then utility
restores, the UPS will return to line mode.
Disable
: After “Disable” is set, once UPS shutdown occurs and the utility restores, the UPS will
not automatically turn on.
Shutdown Delay
: UPS will shut down in setting minutes. The countdown will start after confirming
the pop-up screen.
Restore Delay
: UPS will automatically restart in setting minutes after the UPS shuts down.