28
Mode Name
: Set the UPS model name.
Serial Number
: Set the serial number.
Manufacturer
: Set the UPS manufacturer.
Charger Number
: The number of charging boards installed in the UPS.
NOTE:
It’s required to restart the UPS after setting.
Max Charge CURR
: Set maximum charge current
One piece of charger: 1A – 18A
Two pieces of chargers: 2A – 36A
Three pieces of chargers: 3A – 54A
BATT Number
: The total number of installed battery. (It should be restart UPS after setting.) The
setting range is 16 ~ 20. 16 is default setting.
SYS PARAMETER Page 2
Float VOL
: The setting point of battery float voltage. 13.6V is default setting.
UPS Type
: There are two options, HV and LV. This change is only allowed for qualified technician.
NOTE:
It’s required to restart the UPS after setting.
Power Setting
: Set power factor in percentage.
Output setting
: Set UPS output setting. There are two selections, 3-1 and 3-3.
NOTE:
It’s required to restart the UPS after setting.
Customer Code
: Set customer code.
DynamicPassword
: Enable or disable dynamic password function.
INSTALL INFO
INSTALL INFO Page
SYS Install Date
: Set the date of UPS installation.
BAT Install Date
: Set the date of Battery installation.
Date/Time
: Set
the date and time. The format is YYYY-MM-DD HH:MM:SS. The calendar day will be
automatically changed when the year, month and date are set.