29
VOL CALI
VOL CALI Page1
Bus VOL
: BUS voltage calibration. Each click is 0.1% no matter it’s pressing up or down key
. Press
“up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to confirm the
modification.
BATT VOL
: Battery voltage calibration. Each click is 0.1% no matter it’s pressing up or down key
.
Press “up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to confirm
the modification.
VOL CALI Page2
Line VOL
: Line voltage calibration. Each click is 0.1% no matter it’s pressing up or down key
. Press
“up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to confirm the
modification.
Output VOL
: Output voltage calibration. Each click is 0.1% no matter it’s pressing up or down key
.
Press “up” key to increase 0.1% and press “down” key to decrease 0.1%. Press “OK” key to confirm
the modification.