Battery setting page 1
BATT Warning VOL
:
HIGH
: High battery warning voltage. The setting range is 14.0V ~ 15.0V. 14.4V is default setting.
LOW
: Low battery warning voltage. The setting range is 10.1V ~ 14.0V. 11.4V is default setting.
This parameter setting is related to “Shutdown Voltage” setting. The setting value should be
higher than “Shutdown Voltage” setting.
Shutdown VOL
: If battery voltage is lower than this point in battery mode, UPS will automatically shut
down. The setting range is 10.5V ~ 12.0V. 10.7V is default setting
BATT Age:
Set up battery age.
BATT Parameters
:
BATT AH: Set up battery capacity.
BATT Group: Set up battery group numbers.
Battery setting page 2
Battery Study
: It’s a self-learning function for battery.
Enable
: When enabled, it will calibrate the battery virtual capacity and calculate backup time
according to a complete charging and discharging process.
Disable
: When disabled, the backup time will not be updated during the charging and discharging
process.
Battery Initial
:
Yes:
When selected, the battery virtual capacity will be initialized to 100%. Because battery study
is a self-learning function, after the battery is used for a long time, the virtual capacity of the
battery will be continuously updated based on each full charging process. After replacing the new
battery, the virtual capacity of the battery needs to be initialized.
No:
When selected, the virtual capacity of the battery will not be initialized.
BATT Cali Value
: Calibrate backup time.
BATT TEMP Compensation
: Compensate charging voltage according to battery temperature.