Section 15: Servicing
INSTRUCTION FOR THE HEAT HEATER
PLEASE NOTE SERVICING MUST ONLY BE CARRIED OUT
BY A COMPETENT REGISTERED ENGINEER (CORGI)
BEFORE CARRYING OUT ANY WORK ON THE UNIT SEE
THAT THE ISOLATING SWITCH IS IN THE ‘OFF’ POSITION
AND THE GAS SUPPLY IS SHUT OFF.
BMM HEATERS ONLY RECOMMEND THE USE OF PARTS
SUPPLIED OR RECOMMENDED BY OURSELVES.
INFORMATION IS FOR GUIDANCE OF QUALIFIED
SERVICE ENGINEERS ONLY
Note:
We recommend that the Heater is fully serviced every year and
recommissioned. If the flue gas passages in the heat exchanger, the
combustion chamber, or in the flue chamber are blocked, the Heater can
overheat causing the unit to shut down on the overheat thermostat.
To clean the Heat exchanger:
The heat exchanger must be cleaned from the front and rear of the appliance
after first removing the following items:
(a) The burner assembly
Burner Removal (With gas and electrical supply isolated):
1.
Disconnect the electrical supply to the burner by removing the multi-pin
plug from the socket on the Heater interface panel.
2.
Disconnect gas valve plugs.
3.
Unscrew gas union assembly at inlet to gas train and at entry into burner
mounting flange and remove gas train assembly.
4.
Remove four fixing screws holding burner to heater front and lift
away burner.
32