Troubleshooting Steps and Information 

Each of the following sections have steps that, which in most cases when done in order, will be the best 
route for figuring out an issue. Doing this will ensure there are no conditions external to the battery 
which are causing operation issues. 

Simply skip to the section you are interested in and begin, there is no need to read through every 
section. 

2.1

 

Battery does not turn on 

The battery will never automatically turn on. 

1.

 

Did you press the power switch? 

See below for location of the switch: 

A.

 

Open service cover with screwdriver. 

 

 

B.

 

Look to the upper left side of the plastic fuse holder. 

     

 

C.

 

To switch ON the ESS, hold button for a couple seconds. 
You will see the RED and GREEN LEDs flash once and then the battery will turn on. The 
LEDs should be active (blinking or solid) once the battery is ON. 

 

 

2.

 

I pressed the switch, but the battery still didn’t turn on. 

A.

 

Switch must be held down a couple seconds and the LEDs will light up. 

B.

 

If the LEDs fail to light up after holding the switch down for a couple seconds, then the 
battery or one of its internal components has malfunctioned or failed. 
There could be several different causes for this and additional troubleshooting by BMZ 
will be required. Please contact BMZ. 

Summary of Contents for ESS

Page 1: ...Troubleshooting Guide for BMZ ESS Energy Storage System ...

Page 2: ...21 8499 E mail Service USA bmz group com Firmware 31502A_V2 03 or higher Battery BMZ ESS 7 0 ESS 9 0 ESS X Software ESS 3 0 Service Tool Rev 0 0 27 25617 or higher Country of Origin Germany Phone 49 6188 9956 9830 E mail ess service bmz gmbh de Version 1 01 Subject to modifications BMZ shall not be liable for technical or editorial errors All contents of this document are protected by copyright by...

Page 3: ... 6 2 3 Battery Voltage Issues 6 2 4 Inverter connected to battery will not turn on 7 2 5 Service tool communication error or failure 7 2 6 Battery has been working properly with inverter but has suddenly stopped working and turned off 8 2 7 Battery Temperature 9 2 8 Configuring Batteries in Parallel 10 2 9 The Battery SOC is Wrong 11 2 9 1 The Learning Cycle 11 2 10 Off Grid Systems Battery SOC an...

Page 4: ... to contacting BMZ 1 2 Expected Battery Operation The following is a short list of expected and readily observable battery behaviors under normal operation and are usually no cause for concern Loud click is heard right after the battery is turned on o This is the relay inside the battery closing RED and GREEN LEDs flash once per second o Battery is in standby mode and ready for communication with ...

Page 5: ...location of the switch A Open service cover with screwdriver B Look to the upper left side of the plastic fuse holder C To switch ON the ESS hold button for a couple seconds You will see the RED and GREEN LEDs flash once and then the battery will turn on The LEDs should be active blinking or solid once the battery is ON 2 I pressed the switch but the battery still didn t turn on A Switch must be h...

Page 6: ...elay is closed fuses are inserted and there is still no voltage across the terminals A If above is verified and tested and there is still an issue this very likely indicates some internal issue Please contact BMZ 2 3 Battery Voltage Issues There is always a very small drain on lithium batteries regardless of whether they are in use or not A Battery MUST not sit for too long without being charged o...

Page 7: ...ot use another ESS or battery as a power source for charging C As mentioned above if the battery drops to around 30 volts this is considered the point of no return and the battery will not be recoverable D If you are unable to charge the battery yourself or it has passed the point of no return please contact BMZ if you would like to purchase a replacement or send the battery for disposal 2 The bat...

Page 8: ... some internal issue if all other methods have also failed Please contact BMZ 2 6 Battery has been working properly with inverter but has suddenly stopped working and turned off Normally the inverter is powered by the battery If the battery stops providing power the inverter will shut down If the battery loses communication with the inverter such as if the inverter shut down it will automatically ...

Page 9: ...to these temperature ranges The key caveat to the previous statements is that this range is outside the ESS operational range Exposure to temperatures outside the ESS specified temperature range can cause degradation to the battery lifetime as well as possible triggering of battery protections which may require servicing 1 My battery got too cold or hot what do I do A Allow time for it to warm up ...

Page 10: ...tries to get the setting to save However if you have tried this several times and still the setting will not save there is likely some internal issue Please contact BMZ 2 Ensure the connections are correct A When putting multiple batteries in parallel there should be both power and communication cables connected to every battery once the setup is finished The master battery should be the only batt...

Page 11: ... learning cycle the battery must cover the SOC limits of 100 and 12 as frequently as possible The learning cycle starts at 100 SOC battery full and ends at 12 SOC If both incidents occur in succession and in the meantime the energy is not charged more than 20 SOC then the learning cycle is evaluated as successfully executed What this means is You must charge the battery to 61 5V SOC will automatic...

Page 12: ...tections will trigger at the very end of a charge cycle As of August 2020 this firmware is not on every battery by default so please contact BMZ if you are interested in this firmware and you are off grid 2 11 Battery Capacity Issues BMZ ESS have both nominal and usable capacity listed in the product literature For actual usage usable capacity will always be the value used 1 I get a lower amount o...

Page 13: ...ry weighs approximately 100kg there will be bending of the internal metal structure of the battery It is certainly possible the battery will still work but once this bending occurs there is no way to ensure the physical integrity of the electrical connections inside It s very likely that many internal electrical connections are now loose and therefore compromised This is a hazard If you know an ES...

Page 14: ...Page 2 of 14 Version 1 01 ESS Troubleshooting Guide BMZ GmbH Am Sportplatz 28 30 63791 Karlstein am Main GERMANY Phone 49 6188 9956 0 Fax 49 6188 9956 900 kontakt bmz gmbh de www bmz gmbh de ...

Reviews: