– Ceramic Heater
Before installing this heater, please read all the enclosed instructions carefully and follow any recommendations
regarding installation and use.
Electrical installation
Heaters are factory fitted with high temperature silicon rubber flexible cable conforming to BS 6500 having a
temperature rating of 180°C continuous.
Appliances must be earthed.
The CH fitting has been packed with a separate wall mounting bracket ready for attachment to the heater.
Place heater face down and attach one ‘U’ bracket to back. Make sure cable gland is towards the bottom of the heater.
Location
Heaters should be angled at 30° to 45° from the vertical whether wall or ceiling mounted.
There must always be a minimum clearance of 450mm between top of heater and ceiling.
Wall mounting
Decide whether vertical movement only (Diagram A) or vertical/horizontal movement (Diagram B) is required for
correct positioning of heaters and assemble as shown.
Avoid mounting heaters on structures liable to vibrate.
Recommended mounting heights and safety distances should always be observed.
Recommended Wall Mounting Heights
Model
Wall Mounting Height
(Metres)
Safety Distance from
Heater (Metres)
Minimum
Recommended
Maximum
Minimum
CH-1500
2.2
2.5
3.5
1.5
CH-3000
2.8
3.5
4.5
1.5