26
Remark: the “D1D2” menu appears only if the relays have been assigned to
the D1D2 distribution.
Use the
key to move on to the next parameter:
Choice of impulse length.
Minute 24V standard impulse length (factory configuration) of 1.2
seconds variable from 0.5 to 5 seconds,
Second 24V standard impulse length (factory configuration) of 0.3
seconds variable from 0.1 to 0.9 seconds,
D1D2 standard impulse length (factory configuration) of 6 seconds,
variable from 1 to 10 seconds.
Use the key to move on to the next
parameter:
Choice of status (“Start”/“Stop”).
Circuit stopping must be confirmed.
Use the
key to return to the previous screen.
Caution STOP mode ok
on D1D2 output exit C