31
10) Technical characteristics
Designation
Characteristics
Electrical
Backup
Permanent backup of all parameters in case of mains failure.
Automatic resetting of receiver clocks to correct time after
mains restoration.
Time base
Quartz, accuracy 0.1 seconds per day between 20 and 25°.
Power supply
115 or 230 V AC ± 10% 50/60 Hz or 24 V DC, or 36/72VDC
(depending on the model).
Maximum
consumption
25W, 50W for the model 36/72VDC.
Mains terminals
Cross section 1.5², maximum baring 6 mm.
Earth terminal
Rack: rigid or flexible cable with end piece with cross section 1²
to 1.5²
Wall-mounted: rigid wire 1² to 1.5² bared 6 mm.
Other terminals
Cross section 1.5² maximum, bared 6 mm.
Electrical isolation
Class 1.
Mains power supply
system
TT or TN system.
Order of 3
relay
D1 D2 and alarm.
Relays
Control circuit (relay)
isolation
Galvanic isolation.
Circuit operating
voltage
Either SELV* or LV** with common phase (230 V maximum
between the 2 circuits).
Relay breaking
capacity
240V AC 1A.
Usefulness of
indicator light (of
each circuit)
1) Lit when contact closed.
2) Used to indicate the current circuit programming.
Types of relays
Double-throw (SPDT) on circuit 3.
Normally open (SPNO) on circuits 1 and 2.
Outputs
Synchronisation
Depending on model, on DCF, MSF or GPS antenna.
Minute or half minute
parallel polarised
impulse distribution
1 output 24V 1A, configuration in minute, ½ minute or second
impulse or SR2-59 or TBT 24V power supply.
D1D2 distribution
One output (D1 D2 uses the relays of circuits 1 and 2).
AFNOR coded time
distribution
One output, standard NFS 87 500A (no programming is
necessary) (SELV).