READ AND FOLLOW ALL SAFETY INSTRUCTIONS

! IMPORTANT SAFEGUARDS !

WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY 

PRECAUTIONS SHOULD ALWAYS BE  FOLLOWED, 

INCLUDING THE FOLLOWING:

SAVE THESE INSTRUCTIONS

  1.  Do not use outdoors.
  2.  Do not let power supply cords touch hot surfaces.
 3. This product is suitable for use in damp locations where the ambient temperature is 20ºC minimum, 30ºC maximum.  
    Product is not suitable for heated air outlets and wet or hazardous locations. DO NOT INSTALL NEAR GAS OR  
    ELECTRIC HEATERS. 
  4.  Equipment should be mounted securely in locations and at heights where it will not be readily subjected to  
    tampering by unauthorized personnel. 
  5.  The use of accessory equipment and replacement parts not recommended by the manufacturer may cause an unsafe  
   condition. 
  6.  Do not use this equipment for other than its intended purpose.
  7.  The AC voltage rating of this equipment is 120 or 277 VAC. Do not connect equipment to any other voltage.
  8.  This device complies with Part 15 of the FCC Rules.  Operation is subject to the following two conditions: 
    (1) This device may not cause harmful interference, and  
    (2) This device must accept any interference that may cause undesired operation. 

Consumer Information :

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. 

These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commer-

cial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance 

with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential 

area is likely to cause  harmful interference in which case the user will be required to correct the interference at his own expense. 

You must determine how the connected emergency lighting fixtures are to operate; normally-on (unswitched and 

always energized), normally-off (only energized during a power failure), or switched on/off.  Wire according to the 

appropriate wiring diagram given below. Consult factory for special wiring diagrams.

Ensure that ALL combined/connected Emergency lighting loads OVER this product's maximum emergency output 

rating (250 VA or 185 VA, depending on the model) are capable of being dimmed down to a power output of 10% 

from an industry standard 0-10V source.  

ELI-S-250 WILL ONLY deliver 250 VA and the ELI-S-185 WILL ONLY deliver 185 VA into the lighting load.  This is 

accomplished by automatically dimming the connected emergency lighting loads down to the products output power 

rating.

Pb

THIS PRODUCT INCLUDES RECHARGEABLE LEAD-ACID BATTERIES.  

THE BATTERIES MUST BE RECYCLED OR DISPOSED OF PROPERLY.

! IMPORTANT ! - PLEASE TAKE NOTE BEFORE THE INSTALLATION:

Installation and Operation Instructions

ELI SERIES EMERGENCY LIGHTING INVERTERS

BC

ELI-S-250 & 

Bodine © 2022 Signify Holding. All rights reserved.

Collierville, TN USA • Tech Support 888-263-4638 • Fax 901-853-5009 • www.bodine.com

442295564161

7/8/2022

SELF-TESTING SINEWAVE INVERTER

ELI-S-185 2-Hour

Summary of Contents for ELI Series

Page 1: ...operated in a commer cial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his o...

Page 2: ...ll likely reduce the maximum connected load to something less than 800W As a typical rule of thumb provide at least 10 margin whenever the load specifics are not well known INSTALLATION Illustration 1 below shows the inverter s main circuit board This circuit board contains the enable switch fuse and wir ing terminals Approximate locations of these items are given in Illustration 1 along with deta...

Page 3: ...ge requirements match the output ratings of this product or damage to the load devices may occur CAUTION STEP 2 BATTERY INSTALLATION AND CABLE CONNECTION This product is provided with two sealed lead acid batteries Only the batteries supplied by the inverter manufacturer should be used Install the batteries as shown referring to Illustrations 2A and 2B With the unit secured to the mounting surface...

Page 4: ...gency mode power into the connected load s This is referred to as Auto Dimming When AC power is restored the ELI S 250 ELI S 185 returns to normal charging mode The ELI S 250 operates the emergency lighting load for a minimum of 90 minutes The ELI S 185 operates the emergency lighting load for a minimum of 120 minutes NOTE Driver efficiency and power factor typically fall as dimming level decrease...

Page 5: ...est Switch Two Times Manually initiates a 30 second diagnostic test The inverter will switch to the emergency mode for 30 seconds and test all relevant functions Once complete the inverter returns to normal AC mode and indicate any faults if detected Commissioning Test Press and Release the Test Switch Three Times Initiates a 30 second commissioning test The inverter will switch to the emergency m...

Page 6: ...duct Fuse The fuse contained within this product is field replaceable For the battery fuse location see illustration 1 To replace the fuse disable SW 1 on the inverter then remove AC power from the product Ensure that the battery fuse F101 is replaced by Littelfuse 0312030 312 030 or equivalent 3AG 30 A 32 VDC REPLACEMENT PARTS WIRING DIAGRAM DIMMABLE EMERGENCY LIGHTING SYSTEM Normal only Luminair...

Page 7: ... maximum output power FIGURE W2 7 Normal only Luminaire Normal only Luminaire Normal only Luminaire Normal only Luminaire Norm Emer Luminaire Norm Emer Luminaire Norm Emer Luminaire Norm Emer Luminaire 120 or 277 VAC Out HOT Out COM 120 or 277 VAC Wall Switch SW 1 Inverter ON OFF FGND UNSW HOT COM Neutral SW HOT TOTAL POWER 250W INVERTER ANY QUANTITY SUPPORTED BY THE BRANCH CIRCUIT Non DIMMABLE EM...