FIGURE 10
–
Six different V/F settings.
V/F Pattern for F05 = 001
(50 Hz General Application)
0%
20%
40%
60%
80%
100%
120%
0.1
1
10
100
1000
Output Frequency, Hz
Volts,% of max.
V/F Pattern for F05 = 002
(50 Hz High Starting Torque)
0%
20%
40%
60%
80%
100%
120%
0.1
1
10
100
1000
Output Frequency, Hz
Volts,% of max.
V/F Pattern for F05 = 003
(50 Hz Variable Torque)
0%
20%
40%
60%
80%
100%
120%
0.1
1
10
100
1000
Output Frequency, Hz
Volts,% of max.
V/F Pattern for F05 = 004
(60 Hz General Application)
0%
20%
40%
60%
80%
100%
120%
0.1
1
10
100 1000
Output Frequency, Hz
Voltage, % of max.
V/F Pattern for F05 = 005
(60 Hz High Starting Torque)
0%
20%
40%
60%
80%
100%
120%
0.1
1
10
100
1000
Output Frequency, Hz
Voltage, % of max.
V/F Pattern for F05 = 006
(60 Hz Variable Torque)
0%
20%
40%
60%
80%
100%
120%
0.1
1
10
100
1000
Output Frequency, Hz
Voltage,% of max.
F06: Upper Frequency Limit
Use function F06 to change the upper frequency limit, and hence the maximum
motor speed limit, by changing F06 from the factory setting of “60.0” (60 Hz) to
any number between “01.0” and “200” in increments of 0.1 Hz up to 100 Hz and
increments of 1 Hz after that.
F07: Lower Frequency Limit
Use function F07 to change the lower frequency limit, and hence the minimum
motor speed limit, by changing F07 from the factory setting of “00.0” (0.0 Hz) to
any number between “00.0” and “200” in increments of 0.1 Hz up to 100 Hz and
increments of 1 Hz after that. If F07 > “00.0” and the frequency command < F07,
the inverter will output according to F07 setting.
F08: Preset Speed 1 (SP1) Frequency
Change the frequency of the SP1 input by changing F08 from the factory setting
of “10.0” (10 Hz) to any number between “01.0” and “200” in increments of 0.1
Hz up to 100 Hz and increments of 1 Hz after that. When F19 or F20 = “002”
and the corresponding input terminal is ON, the inverter operates at the
frequency set by F08. The priority of reading frequency setting is: Jog setting
g
SP1 setting
g
keypad setting or external frequency signal
F09: Jog Speed Reference
Use function F09 to change the frequency of the JOG input by changing F09
from the factory setting of “06.0” (6 Hz) to any number between “01.0” and “200”
in increments of 0.1 Hz up to 100 Hz and increments of 1 Hz after that. When
F19 or F20 = “001” and the corresponding input terminal is ON, the inverter
operates at the frequency set by F09. The priority of reading frequency setting
is: Jog setting
g
SP1 setting
g
keypad setting or external frequency signal