F25: Return Drive to Factory Settings
Function number F25 can be used to return all programmable parameters back
to their factory setting (F25 = “020”) or it can be used to configure the control for
the factory settings for 50 Hz power lines (F25 = “010”). F25 is restored back
to “000” after the reset process is complete.
1) When F25 is set to “010”, F05 = “001” and F06 = “050”.
2) When F25 is set to “020”, F05 = “004” and F06 = “060”.
F26: Preset Speed 2 (SP2) Frequency
Use F26 to change from the factory setting of SP2 from “10.0” (10 Hz) to any
number between “01.0” and “200” in increments of 0.1 Hz up to 100 Hz and
increments of 1 Hz after that. When F19 or F20 = “002” and the corresponding
input terminal is ON, the inverter operates at the frequency set by F26. The
priority of reading frequency setting is: Jog setting
g
SP2 setting
g
keypad
setting or external frequency signal
F27: Preset Speed 3 (SP3) Frequency
Use F27 to change the factory setting of SP3 from “10.0” (10 Hz) to any number
between “01.0” and “200” in increments of 0.1 Hz up to 100 Hz and increments
of 1 Hz after that. When F19 or F20 = “002” and the corresponding input
terminal is ON, the inverter operates at the frequency set by F27.