iQ System Display
The iQ system will take a snapshot of the system
performance every 45minutes or if a system adjustment is
made or an alarm is triggered.
Some of the information captured is listed below..
Date
Time
Airflow
Airflow Set point
Pre filter % blocked
Combined filter % blocked
Inlet % (installation restriction)
Motor output
Internal Temperature
Hours run
Alarms
Faults
Date & Time
The date and time will be set as part of the testing stage
with the manufacturer and set to GMT.
Airflow
This column shows the real time airflow through the
extractor.
Airflow set point
Shows the target airflow that has been set by the user, this
will record every time an adjustment is made.
Pre filter % blocked
The display on the extractor will show the pre filter blocking
in 5% increments, but with this downloadable file the pre
filter blockage is shown as an exact percentage of its full
capacity.
Combined filter % blockage
The display on the extractor will show the combined filter
blocking in 5% increments, but with this downloadable file
the combined filter blockage is shown as an exact
percentage of its full capacity.
Inlet % (installation restriction)
Shows the percentage of the iQ system capacity that is
taken up by the installation (pipe work) this value would also
rise if the inlet or pipe work becomes blocked.
Motor output
Shows the percentage the motor is being run at to achieve
the airflow set by the user. This value will increase as the
filters begin to block.
Internal temperature
Shows the internal temperature of the extraction unit, the
sensor is mounted to the main PCB when this sensor
reaches 60
o
C it will shut down the extractor and a log will be
recorded.
Hours Run
This is a simple hours run counter that will begin from the
first time the extraction is switched on by the user. The
hours run counter will only be activated when the motor is
running.
Alarms
When the iQ system has an issue that requires the user to
act upon this is classed as an alarm, when this occurs a code
will appear in this column, the main alarm codes are listed
below.
Code
Meaning
1
Door Open
4
VOC alarm
16
Over temperature
32
Inlet partially blocked
64
Inlet fully blocked
128
No combined filter fitted
512
Motor failure
2048
System 100% blocked
4096
Combined filter blocked
8192
Pre filter blocked
16777216
System 75% blocked
Faults
This column will display a code if a fault with the iQ system
is detected, for analysis of any faults in this column please
contact the BOFA helpline.
.
7
05
Summary of Contents for AD1500 iQ
Page 1: ...AD1500 iQ ...