MOUNTING
When the detector is mounted on a ceiling, it is necessary to follow the requirements of Rules
СП
5.13130.2009, in
particular Table 13.3:
Height
Average Area Monitored by
a Single Detector
Distance
Between Detectors
Between Detector and Wall
Below 3.5 m
Up to 85 sq.meters
9.0 meters
4.5 meters
3.5
÷
6 m
Up to 70 sq.meters
8.5 meters
4.0 meters
6
÷
10 m
Up to 65 sq.meters
8.0 meters
4.0 meters
10
÷
12 m
Up to 55 sq.meters
7.5 meters
3.5 meters
If cannot be installed on a ceiling, the DIP-34PA-03 can be mounted on wire ropes as well as on a wall, a column, or any
other structural. Installing point-type detectors on walls please follow the instructions of Appendix “
П
” of Rules
СП
5.13130.2009.
Figure 2 shows two possible ways of attaching the detector. To attach the detector to a solid surface (variant A) use the
mounting base provided (see also the drilling pattern in Figure 3, at the left). Otherwise, a separately purchased mounting
kit MK-2 can be used to build the detector into a suspended ceiling (variant B). The size of the mounting hole is shown in
Figure 3, at the right.
1:
DIP-34PA-03 Detector
2:
Light Emitter
3:
Alignment Guide
4:
Mark and Bar, OPEN HERE
5:
Base Plate
6:
MK-2 Suspended Ceiling Mounting Kit
(ordered separately)
Figure 3. Drilling Pattern
Figure 3 shows the drilling pattern to
install the detector for the variant A and
the diameter of the mounting hole in the
suspended ceiling for the variant B.
AT T EN T I O N
To install the detector on the base plate, align the guide on the detector with the short guide of the base plate.
Then turn the detector clockwise until the detector guide is aligned with guide 3 as shown in Figure 2 (
А
).
INDICATION
Light Emitter Behavior
Detector Status/Condition
Flashes once per 8 seconds
Norm
Two flashes once per 8 seconds
Fire Alarm or Test
Three flashes once per 8 seconds
Service Required or Trouble
Three flashes (flickering) once per 2 seconds
Indication of undefined (factory set) address in an addressable alarm
loop
Four flashes once per second
Being connected to a non-addressable alarm loop or dc power supply;
or the DIP-34PA-03 is waiting for assigning an address
Figure 2