STANDALONE PHOTOELECTRIC SMOKE ALARM
DIP-34SA
INSTRUCTION MANUAL
1
T E C H N I C A L D A T A
1.1
General
DIP-34SA Photoelectric Smoke Alarm is designed for standalone operation to detect inflammations and issue local audible and light
alarms. The DIP-34SA provides protection of closed areas by sensing smoke registering the light scattered by smoke particles. The
DIP-34A is to be used in a kitchen, near heaters in cottages and so on.
DIP-34SA generates light and high-level sound signals. The alarm indicates low-battery signals, if happened, by periodic short sound
of low intensity.
1.2
Specifications
1.3
Standard Delivery
1)
Detector Sensitivity
- from 0.05 to 0.2 dB/m
Find the following unpacking DIP-34SA:
2)
Alarm Response Time
- 10s max
– DIP-34SA Photoelectric Smoke Alarm
- 1 pc.
3)
Consumed Current
- 0.01 mA max
– ECT UY Connectors
- 2 pcs.
4)
Technical Readiness Time
- 60 s max
– Woodscrews
- 2 pcs.
5)
Input Power
- 9V
– Wall Plugs
- 2 pcs.
6)
Operating Temperatures
- from
−
10 to +55
°
С
– 6F22 9v Battery
- 1 pc.
7)
Relative Humidity
- up to 93% at +40
°
С
– Instruction Manual
- 1 pc.
8)
Overall Dimensions
– diameter
- 102 mm max
– height
- 35 mm max
9)
Weight
- 0.2 kg max
2
O P E R A T I O N I N S T R U C T I O N S
2.1
Mounting
To attach the smoke alarm base to the ceiling, drill two holes of 5
мм
in diameter, with the distance between the centers of holes
being equal to 40–70 mm. Insert the wall plugs provided into the holes and fasten the device base to the ceiling with the woodscrews
provided.
DIP-34SA alarms are to be installed on ceilings at distances no more than 4.5
м
from walls. Being installed at heights up to 3.5
m, a single DIP-34SA covers approximately 85
м
².
Alarms can be combined together by a two wire line in a group up to 38 units. In such case a response of a single smoke alarm
causes other alarms from the group to sound too. The alarms are bounded by connecting wires within them. Be careful to match colors
while connecting the wires. The wires are connected to the connecting line by crimping wires in connectors provided.
2.2
Testing
The DIP-34SA smoke alarm is equipped with a latch on its enclosure in order to prevent DIP-34SA mounting without a battery.
The detector is delivered with the battery being attached under its base. Connect the battery to the terminal block before
testing DIP-34SA smoke alarm.
After battery’s having been connected a sound alarm can be issued within a second. Please wait until the LED flashes that means
entering to the quiescent mode. Press TEST button and hold it pressed for about 5 second until LED flashes and sound alarm goes off.
The sound must be loud interrupted one. This means that the detector operates correctly.
Otherwise, if the test procedure failed, disconnect the battery and wait for 5 minutes before connecting this one again to repeat
testing.
If the test has been completed successfully, install the detector on the base and inspect visually periodical (approximately once
per 30 s) LED flashes confirming detector’s entering normal quiescent mode.
2.3
Maintenance
Test the detector periodically by pressing TEST button until sound alarm goes off. This can take up to 20 seconds. It is the
only way to ensure that the detector operates properly.
Appearing of a periodical weak short sound signal indicates that power supply voltage has dropped and the battery must
be replaced.
3
W A R R A N T Y
3.1
The average lifetime of the smoke alarm is at least 10 years.
3.2
The manufacturers warrants its product to be free from defects in materials and workmanship under normal use and service
for 18 months since putting it into operation, but no more since 24 months since acceptance date.
3.3
In the event of in-warranty failure forward your claims to the address:
ZAO NVP Bolid
4 Pionerskaya Str., Korolev 141070, Moscow Region, Russia
Tel./Fax: +7 (495) 775-71-55, +7 (495) 516-93-72
E-mail:
info@bolid.ru
http://
www.bolid.com
.