RIP Current Status 

POWER 

LED 

CHARGE 

LED 

24 V LED 

Sounder 

Human Action 

Normal mains 
power, the batteries 
are charged 

ON 

OFF 

ON 

OFF 

– 

Normal mains 
power, a short 
circuit failure 
(overload) at the 
output for more than 
3 s 

Flashes 

every 1-2 s 

OFF 

OFF

 

Beeps twice 

every 1-2 s 

Repair load 

failure 

AC power failed, an 
output short failure 
or overload 

OFF 

OFF 

OFF 

OFF 

Repair load 

failure 

AC power failed, 
the battery voltage 
is above 22 V 

OFF 

OFF 

ON 

Beeps once 

every 4-5 s 

Check operability 

of the F1 fuse and 

repair mains 

power 

AC power failed, 
the battery voltage 
is above 22 V 

OFF 

OFF 

ON 

Beeps once 

every 0.5-1 s 

Repair mains 

power 

AC power failed, 
the batteries are 
discharged 

OFF 

Flashes 

once every 

1-2 s 

OFF 

On 

After recovering 

mains power, test 

the battery 

charge-discharge 

cycle * 

Note:

 

–  * After  disconnecting  the  batteries  from  the  load  circuit  and 

recovering  utility  power  it  is  recommended  to  check  the  battery 
charge-discharge  cycle.  If  the  CHARGE  LED  has  been  still  lit  after 
24 hours since having restored power then the battery operability has 
been  to  be  checked.  If  extra  batteries  are  connected  the  charge  time 
will be increased. 

2.3.3

 

How to Turn the RIP Off 

а

)

 

Turn off the mains power 220 V. 

б

)

 

Disconnect the batteries. 

в

)

 

Remove the fuse F1. 

г

)

 

Disconnect the load. 

3

 

MAINTENANCE 

Preventive maintenance of the RIP should be carried out at least annually. Maintenance 

works are to be performed by a service company employee and include: 

1)

 

Visual inspection of the RIP; 

2)

 

Checking  the  output  voltage  value  when  the  load  is  connected  as  specified  in 

Section 1.2.3 of this Manual and checking the output voltage value when the RIP is powered 
by batteries; 

3)

 

Testing LED and sound indication as per Table 1 of this Manual; 

Summary of Contents for RIP-24

Page 1: ... GOST 15150 69 but to be used within temperature ranges of 263 К to 313 К 10 С to 40 С and ambient humidity of up to 90 at 298 К 25 С 1 1 6 In terms of mechanical tolerance the RIP corresponds to Category LX in accordance with GOST 12997 84 vibration within 1Hz to 35 Hz when accelerated up to 4 9 m s2 0 5 g 1 2 Specifications 1 2 1 The main power supply is the mains power 150 253 V 50Hz 1 2 2 The ...

Page 2: ...ra 12 V batteries of 17 Ah each placed in a special Box 24 Mod 0 to increase the time of operation from the batteries with total capacity of all RIP batteries being equal to 2 24 Ah 1 2 16 The RIP provides immunity to electromagnetic interference of the third severity level according to Russian Standard GOST R 50009 2000 1 2 17 Radio disturbances from the RIP operation do not exceed the values spe...

Page 3: ... third or higher safety qualification level can mount and maintain the RIP CAUTION Connecting the RIP to the mains utility power please KEEP UP the correct coupling of LINE and NEUTRAL TERMINALS in agreement with the picture located inside the cabinet closely to power terminal block 2 2 Mounting and Preparing for Operation 2 2 1 The RIP is to be installed on walls or other structures in the protec...

Page 4: ...rder to indicate remotely switching the RIP to backup power or a short circuit failure connect the RIP to the alarm loop of the devices to be powered An example of connecting the RIP with alarm loops of such devices as Signal 20P S2000 4 and similar is shown in Figure 2 A termination resistor 4 7 K provided with the devices is to be installed inside the RIP XP2 XP3 RED Output 27V 3A Line Neutral X...

Page 5: ...mains power supply fails the batteries begin to power the load circuit the 24 V indicator being turned on and the sounder going off periodically The POWER and CHARGE indicators are off e If the voltage of the batteries has dropped to 22 V the sounder switches on and off five to ten times more rapidly It is necessary to take measures to restore mains power line as soon as possible f If the voltage ...

Page 6: ...arge discharge cycle Note After disconnecting the batteries from the load circuit and recovering utility power it is recommended to check the battery charge discharge cycle If the CHARGE LED has been still lit after 24 hours since having restored power then the battery operability has been to be checked If extra batteries are connected the charge time will be increased 2 3 3 How to Turn the RIP Of...

Page 7: ...e technical support 7 495 775 71 55 or e mail support bolid ru 4 4 When submitting the product for repair it shall be accompanied with descriptions of possible fault Claims shall be submitted to the following address NVP BOLID CJSC Pionerskaya 4 Korolyov city Moscow region Russia 141070 Phone fax 495 775 71 55 multiline 516 93 72 E mail info bolid ru Support support bolid ru http bolid ru 5 CERTIF...

Page 8: ...ts of state standards and applicable technical documentation and approved as ready for operation 6 2 Battery Backed Power Supply RIP 24 model 01 RIP 24 3 7M4 is packaged by CJSC NVP Bolid in line with the requirements provided in the current technical documentation Responsible for acceptance and packaging QCD _____________________________ ________________________ Full Name Data Month Year ...

Reviews: