background image

18 

 

4

 

Repair 

Repair of faulty equipment is to be conducted by the manufacturer or in authorized repair centers. 

The  product shall  be sent  for  repair in  compliance  with  Company  Standard  QMS  8.5.3-2015, which 
can be found online at our website 

https://bolid.ru/support/remont/.

 

An  equipment  fault  resulted  from  consumer’s  not  observing  rules  of  mounting  and  operation  is 

not a reason for claims and warranty repair. 

Claims shall be submitted to the following address: 
NVP BOLID, #4 Pionerskaya Str., Korolyov, Moscow Region, 141070, Russia 
Phone: +7 (495) 775-71-55, E-mail: 

info@bolid.ru

In case of any issue related to use of the product, please contact the technical support: +7 (495) 

775-71-55 or e-mail 

support@bolid.ru.

 

5

 

Storage 

Storage in a transport container is permitted at ambient temperatures minus 50 t 55 

°

С

 

and relative humidity up to 95% at + 35 

°

С

Storage in the consumer package is permitted only in heated premises at temper5 through 

+40 

°

С

 and relative humidity up to 80% at + 20 

°

С

6

 

Transporting 

The units can be transported in a transport container at ambient temperatures minus 50 up to + 55 

°

С

 and relative humidity up to 95% at + 35 

°

С

7

 

Disposal 

The unit can be disposed of considering that there are no toxic components in it.  
The  content  of  precious  materials:  doesn’t  require  accountability  for  storage,  retirement,  and 

disposal (Clause 1.2 of GOST 2.608-78).  

The  content  of  non-ferrous  metals:  does  not  require  accountability  for  retirement  and  further 

disposal. 

8

 

Manufacturer Warranty 

The manufacturer guaranties the product meets with technical requirements stated in the manuals 

if the user follows the instructions for transportation, storage, installation, and usage. 

The  warranty  period  is  18  months  since  putting  the  product into  operation  but  no  more than  24 

months from the manufacturer’s date of production. 

9

 

Certification Information 

S2000-SP2  Rev.02  Addressable  Two  Output  Alarm  Actuating  Unit  meets  the  requirements  of 

Technical Regulations of Eurasian Economic Union TR EAEU 043/2017 ‘On Requirements for Fire 

 

Warning! 

The  equipment  shall  be  submitted  for  repair  being  assembled  and  clean  and  along 

with all the parts listed in the documentation. 

Claims  are  accepted  only  if  a  reclamation  report  describing  the  failure  is  applied  to 

the submitted equipment. 

Summary of Contents for S2000-SP2

Page 1: ...ADDRESSABLE TWO OUTPUT ALARM ACTUATING UNIT S2000 SP2 Rev 02 User s Manual ...

Page 2: ... 9 2 2 1 Safety Precautions 9 2 2 2 Design 9 2 2 3 Mounting the Unit 10 2 2 4 Wiring the Unit 12 2 2 5 Programming the Unit 13 2 2 6 Usage 15 2 2 7 Testing Operability 15 2 2 8 Extreme Situation Actions 16 2 2 9 Troubleshooting 16 3 Maintenance 17 3 1 General 17 3 2 Safety Precautions 17 3 3 Maintenance Procedures 17 3 4 Testing Operability 17 3 5 Technical Examination 17 3 6 Preservation Depreser...

Page 3: ...the personnel who have studied this manual are allowed to operation activities All activities on mounting start up programming and testing shall be performed in compliance with the requirements of the regulatory documentation in force at the place of operation Abbreviations CIE Control and Indicating Equipment ISS Integrated Security System PL Multiplex Addressable Polling Loop ...

Page 4: ...ms The unit is used with an S2000 KDL or S2000 KDL 2I polling loop controller under an S2000M control panel or Sirius Fire Alarm Control Panel or one of their modifications as a component of modular control and indicating equipment in such system as a fire intrusion panic alarm system a voice fire alarm and evacuation system a fire suppression and smoke control system an access control system a CC...

Page 5: ...y of the executive part Enclosure Protection Degree as per GOST 14254 2015 IP40 Resistance to mechanical exposure as per OST 25 1099 83 Arrangement Category III Vibration exposure Frequency range Max acceleration 1 35 Hz for Category III 0 5 g for Category III Environmental category as per OST 25 1099 83 O3 Operating temperatures Minus 30 through 55 С Weight 0 2 kg max Overall dimensions 102 107 3...

Page 6: ...relatively to the 0V terminal Normal between minus 0 15 V and minus 1 125 V Open Circuit Fault less than minus 1 125 V Short Circuit Fault higher than minus 0 15 V Status of a switched on monitored circuit is defined by the value of monitored circuit current Normal between 5 mA and 3 A Open Circuit Fault less than 5 mA Short Circuit Fault higher than 3 A Note If an output while being switched on i...

Page 7: ...1 5 Measuring Instruments Tools and Accessories While mounting commissioning and maintaining the equipment one should use the instruments tools and accessories shown in Table 1 5 1 Table 1 5 1 Instrument Specifications Digital multimeter AC DC voltage up to 500 V AC DC current up to 5 A resistance up to 2 MOhm Flat head insulated screwdriver ZUBR ELECTRO EXPERT SL 3 0х75 mm Cross slot insulated sc...

Page 8: ...g emergency operation in accordance with Russian standards GOST 12 2 007 0 75 and GOST 12 1 004 91 The unit has no circuits under a hazardous voltage Do SHUT OFF power from the equipment before mounting installing and maintaining this one Installation and maintenance of the unit shall be carried out by professionals qualified for Accident Prevention of Class II or higher 2 2 2 Design The unit is c...

Page 9: ...acently vertical and horizontal distances between them shall be at least 10 mm each The design of the unit doesn t provide its operation in aggressive and or dusty environments as well as in explosion hazardous and flammable premises The unit shall be installed at a height suitable for operating and maintenance Installation and maintenance of the unit shall be carried out by professionals qualifie...

Page 10: ...nnect electric wires to the unit as per the project design documentation and the connection diagram Close the unit with its cover To dismantle the unit please follow all the steps in the reverse order Mounting on a DIN rail Install the unit on the DIN rail Remove the cover from the unit Connect electric wires to the unit as per the project design documentation and the connection diagram Close the ...

Page 11: ...stems or equipment in explosion protected housing load connection modules can be installed in close vicinity from them 4 If an output is not in use one can replace load connection module with a 510 Ohm 1 2W resistor Figure 2 2 5 General Schematic for Connecting the Unit Connecting to fixed fire fighting systems should be conducted in accordance with the schematic in Figure 2 2 6 The length of wire...

Page 12: ... so on can be connected in parallel across a single output if the following requirements are met In the quiescent mode the appliances are turned off The total current per the output doesn t exceed the maximum allowed one 3 A Mounting is conducted in accordance with the schematic shown in Figure 2 2 7 Figure 2 2 7 The Diagram for Connecting Several Normally Turned Off Sirens or Light Signs to a Sin...

Page 13: ...controller they are to be defined on the Outputs tab of UProg Configuration Tool The list of the configuration parameters is presented in Table 2 2 1 Specific values of the configuration parameters to be defined are to be selected depending on the type of the actuating devices connected to the unit and the requirements for their operation in scope of the specific project To have more details on th...

Page 14: ...To change configuration parameters please use UProg utility v 4 1 0 26 2 2 6 Usage The unit is operated under an S2000 KDL polling loop controller and S2000M control panel or Sirius fire alarm control panel All operating conditions control program time to operate delay before operating the output are defined by configuration parameters of the equipment mentioned above To get information how to def...

Page 15: ...it failure Replace the unit for a healthy one following the instructions of this manual No power for executive part of the unit Check the power voltage at the unit power inputs The unit address is not shown in the UProg utility Collision of addresses of various addressable devices in the polling loop Set the unit address to another value the value should be between 1 and 123 Warning If sparks fire...

Page 16: ...oupled with automated fire fighting equipment shall be disconnected from the outputs of the unit and be replaced with the simulators similar in the load current After applying power to the unit the built in indicator READY start lighting steady until the moment the polling loop controller polls the given address Then the indicator goes to flash slowly Remove the cover from the unit and ensure that...

Page 17: ...transport container at ambient temperatures minus 50 up to 55 С and relative humidity up to 95 at 35 С 7 Disposal The unit can be disposed of considering that there are no toxic components in it The content of precious materials doesn t require accountability for storage retirement and disposal Clause 1 2 of GOST 2 608 78 The content of non ferrous metals does not require accountability for retire...

Page 18: ...ut Alarm Actuating Unit meets the requirements of Technical Regulations of Custom Union Electromagnetic Compatibility of Technical Equipment TR CU 020 2011 It is covered by the conformity declaration ЕАЭС No RU Д RU HP15 B 06633 20 Production of S2000 SP2 rev 02 is awarded with the conformity certificate GOST R ISO 9001 The certificate can be found online at the website http bolid ru in the sectio...

Reviews: