Addressable Radio Link System
www.bolid.ru
84
Table 10-38. Link Quality Indication
RADIO LED Performance
Condition
Flashes with green
Strong signal
Flashes with green and red
Normal signal
Flashes with red
Weak signal (not recommended to install)
Shows solid red light for 1 s
No communications or the device is not connected to
the ARR32
Getting Started
Open the module case and remove the insulating spacer from the battery holder. Wait until
depassivation is completed.
The depassivation procedure activates the battery after long term storage and can take up to 5
minutes. The process of depassivation is indicated as shown in Table 10-35. If depassivation fails the
module indicates a power supply discharge.
Connecting and Programming
Connect the module to the ARR32 and set its parameters in the configuration of the polling loop
controller as discussed in Sections 6, 7, and 8 of this Manual.
The S2000R-RM occupies two or three addresses within the polling loop of the polling loop controller:
The first address for Relay 1;
The second address for Relay 2;
The third address for Monitored Circuit (if connected).
External Button and Monitored Circuit (MC)
The S2000R-RM provides connecting an external button to control Relay 1 manually or external
detectors with dry contact outputs.
To select the Detector or Button mode, set MC Mode jumper in the relevant position (see Table
10-39) and then connect the relay module to the ARR32. The current mode is stored in the non-
volatile memory and can be changed only after re-connecting to the ARR32 (see Section 6).
Table 10-39. MC Mode Jumper Positions
Jumper Position
Monitored Circuit Mode
Position «1»
Detector (a detector with dry contact output).
Position «2» or open
Button (a button for activation Relay 1 manually).
In the Button mode, Relay 1 flips to the opposite state when the input of Monitored Circuit is closed for
more than a half of a second.