Input and output fuses on the fan transformer. These will be located on
or around the fan transformer itself.
•
Check fan for blockage. Clean if necessary.
•
Check fan transformer primary voltage and ensure it is within tolerance
for the control voltage input for that module.
•
Replace fan.
•
If fan still doesn’t operate, the heatsink temperature switch may be faulty.
Contact Bonitron for return for repair.
5.3.6.
C
ONTROL
R
EADY CONTACTS WON
’
T CLOSE
If the status contacts listed in Section 4.2.3.2 will not close, this indicates one
of the following conditions:
•
Loss of Control Power
•
Failure in control circuit
5.3.7.
P
OWER
S
TAGE
R
EADY CONTACTS WON
’
T CLOSE
•
Over-temperature in module
•
Shorted IGBT (power transistor)
•
IOC fault
The R7E option has each of these conditions broken out as separate status
contacts. Refer to Section 3.4.2 for locations and status indicated.
If the over-temperature contacts will not close, check the temperature of the
module see Section 5.3.8 below for overheating troubleshooting. If the
module is hot, wait for the module to cool and see if it begins to function
properly.
If one of the other contacts is open, and will not close, the module has a fault
that needs to be repaired by Bonitron. Contact Bonitron for assistance.
If the module is cool and still will not operate, contact Bonitron for assistance
or repair.
5.3.8.
M
ODULE OVER
-
TEMP
,
OR MODULE SEEMS TOO HOT
It is normal for this module to produce heat. Temperatures of 150°F are not
uncommon. If the modules fan is running, and the module is operating
properly, it is within normal tolerances.
If you have the R7E option, check the contacts at TB4-5&6. If the contacts
are open, then the module is inhibited due to over-temperature. If the fan is
not running, see Section 5.3.5 above for assistance.
If the fan is running, check to make sure the airflow through and around the
module is unobstructed.
If the ambient temperature is high in the cabinet or installation area, the
module may overheat. Make sure the environment is within the operating
temperature requirements listed in the General Specifications (Table 2-6).
Summary of Contents for M3452
Page 14: ...M3452 vR7 EIP PDP 14 This page intentionally left blank ...
Page 19: ...User s Manual 19 Figure 3 2 Customer Connections in K9 Chassis CUSTOMER I 0 CONNECTION ...
Page 21: ...User s Manual 21 Figure 3 2 Customer Connections in M14 Chassis CUSTOMER I O CONNECTION ...
Page 24: ...M3452 vR7 EIP PDP 24 Figure 3 6 I O Hookup with R7 EIP PDP Communication ...
Page 26: ...M3452 vR7 EIP PDP 26 Figure 3 8 24VDC Power Connection ...
Page 58: ...M3452 vR7 EIP PDP 58 This page intentionally left blank ...
Page 66: ...M3452 vR7 EIP PDP 66 Figure 6 3 M3452 K9 Chassis Dimensional Outline Drawing ...
Page 68: ...M3452 vR7 EIP PDP 68 Figure 6 5 M3452 M14 Chassis Dimensional Outline Drawing ...
Page 75: ...User s Manual 75 NOTES ...
Page 76: ...M3452 vR7 EIP PDP 76 This page intentionally left blank ...
Page 77: ......
Page 78: ......
Page 79: ......