User’s Manual
15
3.
I
NSTALLATION
I
NSTRUCTIONS
CAUTION!
Installation and/or removal of this product should only be performed by a
qualified electrician in accordance with National Electrical Code or local
codes and regulations.
Proper installation of the M3645P DC bus power supply modules should be executed
following the steps outlined below. Be sure to refer to the AC drive instruction manual as
these steps are performed. Please direct all installation inquiries that may arise during the
installation and start-up of this product to the equipment supplier or system integrator.
3.1.
E
NVIRONMENT
The module should be installed in an area protected from moisture and falling debris.
Buildup of dust or debris may cause poor performance and possibly a failure.
Operating in a wet environment can pose a shock hazard. The recommended
temperature range for operating this module is 0 to +40
C.
Device shall be installed in a pollution degree 2 environment.
3.2.
U
NPACKING
Upon receipt of this product, please verify that the product received matches the
product that was ordered and that there is no obvious physical damage to the unit. If
the wrong product was received or the product is damaged in any way, please contact
the supplier from which the product was purchased.
3.3.
M
OUNTING
3.3.1.
M3645P
DC
B
US
R
EGENERATIVE
P
OWER
S
UPPLY
The installation site for the M3645P power supply should be chosen with several
considerations in mind:
•
When mounting regen units in an enclosure, power dissipation should be taken
into account. Refer to Section 6.3 Watt Loss for details.
•
The unit requires a minimum clearance of two (2) inches in all directions around it
when not mounted near a heat source. Heat sources may increase necessary
clearances.
•
Unit should not be exposed to falling debris or condensation.
Once the installation site has been selected as outlined above, the unit should be
mounted in place.
The M3645P must be properly oriented for proper heat flow through the unit. The
M3645P must be mounted with the rear surface of the unit to the mounting surface.
The unit may be mounted vertically (Figure 3-1D), or with its backplane down and
parallel to the ground (Figure 3-1A).
Do Not
mount the unit on the underside of a mounting surface as shown in Figure 3-
1B.
Do Not
mount the unit in a horizontal position with its side parallel to the mounting
surface or floor as shown in Figure 3-1C.
Do Not
mount the unit in an upside-down position, as shown in Figure 3-1E.
Refer to Table 2-3: Chassis Styles to determine the chassis for the unit. Mounting
dimensions and provisions vary by unit chassis. See Figure 3-1 for mounting
orientation information and Section 6.6 for dimensional drawings.
Summary of Contents for M3645P
Page 14: ...M3645P 14 This page intentionally left blank ...
Page 22: ...M3645P 22 Figure 3 5 M3645P 150A 225A and 300A Connection Locations ...
Page 27: ...User s Manual 27 Figure 3 9 M3645P 150A 225A and 300A Power Wiring ...
Page 30: ...M3645P 30 This page intentionally left blank ...
Page 45: ...User s Manual 45 Figure 6 2 M3645P M11 Chassis Dimensional Outline ...
Page 46: ...M3645P 46 Figure 6 3 M3645P M12 Chassis Dimensional Outline ...
Page 47: ...User s Manual 47 Figure 6 4 M3645P M15 Dimensional Outline ...
Page 48: ...M3645P 48 Figure 6 5 M3645 M15 Line Reactor Dimensional Outline ...
Page 50: ...M3645P 50 6 7 BLOCK DIAGRAM Figure 6 7 Typical Customer Application ...
Page 53: ...User s Manual 53 NOTES ...
Page 54: ...M3645P 54 ...
Page 55: ......