User’s Manual
17
3.3.2.
M3645
M15
L
INE
R
EACTOR
M
OUNTING
The installation of the M3645 M15 line reactor should be chosen with several
considerations in mind:
•
The M3645 M15 line reactor is only required when using the 150A, 225A, and
300A rated M3645 in the M15 chassis.
•
When mounting the line reactor in an enclosure, power dissipation should be
taken into account. Refer to Section 6.3 Watt Loss for details.
•
The unit requires a minimum clearance
of two inches (2”) in all directions around
it when not mounted near a heat source. Heat sources may increase necessary
clearances.
•
Unit should not be exposed to falling debris or condensation.
•
The unit can be mounted in any orientation.
Once the installation site has been selected as outlined above, the unit should be
mounted in place. See Section 6.6 for dimensional drawings.
3.3.3.
KIT
3645DD,
E
XTERNAL
D
ISPLAY
M
OUNTING
The KIT 3645DD external display is comprised of the display board assembly (ASM
3645D3) and a 12-foot-long cable (CBL 3660DD4-DI12). The installation should be
chosen with several considerations in mind:
•
The external display requires a cutout from the front panel. See Figure 6-6 for the
dimensional requirements for the cutout.
•
The display will attach to the front of the panel. The display is secured to the
panel with a screw in each corner.
•
The unit requires a minimum clearance of one (1) inch in all directions around it.
•
The unit should not be exposed to falling debris or condensation.
•
The 12-foot cable provided with the display must be attached to TB5 on the
control board of the M3645P and to TB3 on the ASM 3645D3 on the rear of the
display. See Figure 3-12.
Once the installation site has been selected as outlined above, the unit should be
mounted in place. See Section 6.6 for dimensional drawings.
NOTE:
The KIT 3645DD is only compatible with “L” versions of the M3645P power
supply. Only a single display can be used for each line regen. The line regen is unable
to power more than a single display.
3.4.
W
IRING AND
C
USTOMER
C
ONNECTIONS
Be sure to review all pertinent AC drive and system documentation as well as the
information listed below before proceeding. Connection points and terminal numbers
of the AC drive will be found in the documentation provided with those units. See
Tables 3-1 thru 3-6 and Figures 3-2 thru 3-8 for connection details.
3.4.1.
P
OWER
W
IRING
CAUTION!
Only qualified electricians should perform and maintain the interconnection
wiring of this product. All wiring should be in accordance with local codes.
DANGER!
Do NOT daisy chain the AC, DC, or ground connections between multiple
power supply units. Each power supply should have separate power and
ground connections.
Summary of Contents for M3645P
Page 14: ...M3645P 14 This page intentionally left blank ...
Page 22: ...M3645P 22 Figure 3 5 M3645P 150A 225A and 300A Connection Locations ...
Page 27: ...User s Manual 27 Figure 3 9 M3645P 150A 225A and 300A Power Wiring ...
Page 30: ...M3645P 30 This page intentionally left blank ...
Page 45: ...User s Manual 45 Figure 6 2 M3645P M11 Chassis Dimensional Outline ...
Page 46: ...M3645P 46 Figure 6 3 M3645P M12 Chassis Dimensional Outline ...
Page 47: ...User s Manual 47 Figure 6 4 M3645P M15 Dimensional Outline ...
Page 48: ...M3645P 48 Figure 6 5 M3645 M15 Line Reactor Dimensional Outline ...
Page 50: ...M3645P 50 6 7 BLOCK DIAGRAM Figure 6 7 Typical Customer Application ...
Page 53: ...User s Manual 53 NOTES ...
Page 54: ...M3645P 54 ...
Page 55: ......