Speedlane 900
Edition:
SL900 -OIM - USA
6.3.2 External
Mains power.
The mains power is connected to the terminal strip located in the master unit.
Terminals are labelled L
– N and the PE sign.
Fire alarm.
The fire alarm contact needs to be a N.C. (Normally Closed) contact.
It is connected directly to the microcontroller board
Fire alarm
connector D
– terminal 15 & 16.
Access control
Authorization pulses In and Out are connected directly to the microcontroller board.
Pulse In
connector F
– terminal 16 & 17.
Pulse Out
connector E
– terminal 16 & 17.
Return Signal In
connector F
– terminal 11 & 12.
Return Signal Out
connector E
– terminal 11 & 12.
Alarm contact can be connected to the relay’s.
General alarm
Relay K0
– terminal 11 common, 12 N.C., 14 N.O.
Intruder alarm In
Relay K1
– terminal 11 common, 12 N.C., 14 N.O.
Intruder alarm Out
Relay K2
– terminal 11 common, 12 N.C., 14 N.O.