Page:
44
OIM - Manual
Version:
2014/11
Speedlane 900
Edition:
SL900 -OIM - USA
7.5 Start-up
WARNING!
No persons should stand in the Speedlane 900 during the Start-up
procedure, as all safety features are temporarily disabled.
Generally, the Speedlane 900 will be pre-configured by Boon Edam and is ready for use after proper
installation. Any user programmable settings have been set to their default values and need no
further adjustment. Setting up the Speedlane 900 for operation can be accomplished by using the
start procedure as described below.
Ensure the Speedlane 900 has been placed and installed correctly.
Ensure that the main switch is off (located next to the MCB).
Ensure that the electrical connections have been made as described.
Switch on the UPS by pressing its POWER button, located at the bottom of the UPS
Switch the power on with the main switch.
The Speedlane 900 starts to initialise, enabling the encoder to determine its range,
as a result the door wings open and close.
Do not stand in the Speedlane 900 during the initialisation process.
While the Speedlane 900 is initialising all security features will be disabled.
Wait for the product to take its starting position.
Check the security and safety.
Check the operation of the Speedlane 900.
Perform the running in of the Speedlane 900.
When a door wing is blocked while it is closing, the door will re-open automatically and attempt to
close 3 times. After 3 times the traffic indication signals will blink red. When this happens, the power
needs to be switched off or reset sequence is pushed and the obstacle removed. Then the start-up
procedure can be activated again.
7.5.1 Calibration sequence
The correct calibration sequence is that:
The door wings first open and then close.
If this is not the calibration sequence, then the motor phases have to be switched.
7.5.2 Testing
Testing the operation of the Speedlane 900.
Test and activate the following user inputs: card in, card out, free in, free out, open, block in, block
out and fire alarm.
Check the following UPS inputs: battery low and power failure (UPS connector D pins 3, 4 (ground)
and 5).
7.5.3 Running in
It is recommended that after installation a period of supervised running in is carried out to test for
any installation or technical problems. To enter the running in mode press the Escape button on
the main control board for 3 seconds. Pressing the Escape button again will stop the running in
sequence.
A 5 minutes running in period is recommended.