5.8 Electrical installation
The requirements for the mains power supply are:
•
Power supply: 110-240 VAC, 50/60 Hz (
Verify correct Voltage with your order
)
•
Internal Fuse of MCB: 15A
•
Recommended Breaker: 20 amp single pole (110VAC), Double pole (<200VAC).
•
Refer to the electrical drawings (E-drawings) for more detailed information.
Mains Electrical Connection
Electrical service conduit holes are designed into both mid-posts of the THT-100. There are two
holes on each side for running mains power, access control, fire alarm or other necessary
communications to the unit. The Endposts and Midpost and Barrier post also function as a
conduit for channeling electrical wires from the ground up into the control box.
A standard electrical cable is supplied with the unit which connects to the control box. Connect
in accordance with local electrical code requirements. The following components are included
for connection of the controls to the building system:
Figure 5-16: Main Control Box
Wire Strainers for ACS
On/Off Switch
Receptacle for Mains Connection
Figure 5-15: Conduit Holes