6 Electrical
connection
6.1 Power supply voltage
- The transmitter type TR must be supplied with 24 V DC, 2-wire technique.
- Terminal voltage 14 to 30 V DC (terminals 1 and 2)
- Recommendation: 2-wire cables, twisted and shielded
(cable diameter 6-12 mm)
- Ground cable shield according to section 16.1
Wiring diagram.
- In order to ensure safe HART
communication, the limits for the
minimum load with R
L
≥
250
Ω
must be observed.
- For the maximum amount of line and load resistance, see diagram below.
The maximum load depends on the supply voltage.
A
V
U
R
V
U
For
A
V
U
R
V
U
For
B
B
B
B
022
.
0
)
5
.
8
(
:
2
.
15
004
.
0
)
14
(
:
2
.
15
−
=
≥
−
=
<
Maximum load
0
200
400
600
800
1000
14
16
18
20
22
24
26
28
30
Supply voltage [V]
Load [ohm]