UPS user manual
Utilizzo dell’UPS
42
OMD10082 REV. F
Alarm
A17
RETRANSFER BLOCK
Description
The load is blocked on the bypass line.
Possible
causes
Very frequent changeovers due to load in-rush currents.
Static switch problems.
Solutions
1. Reset the system.
2. Check the in-rush currents of the loads.
3. If the alarm persists, contact our Technical Support Service.
Alarm
A18
MBCB CLOSED
Description
The manual bypass isolator is closed.
Possible
causes
Manual bypass isolator closed.
Solutions
1. Check the status of the manual bypass isolator.
2. Check the functionality of the auxiliary contact of the isolator.
3. If the alarm persists, contact our Technical Support Service.
Alarm
A19
OCB OPEN
Description
The output isolator is open.
Possible
causes
Output isolator open.
Solutions
1. Check the status of the output isolator.
2. Check the functionality of the auxiliary contact of the isolator.
3. If the alarm persists, contact our Technical Support Service.
Alarm
A20
OVERLOAD
Description
The current sensor has detected an overload at the output. If the alarm
persists, the thermal image protection will be activated (alarm A21).
Possible
causes
Output overload.
Measuring circuit failure.
Solutions
1. Check the loads connected to the UPS output.
2. Contact our Technical Support Service.
Summary of Contents for ASD10
Page 1: ...OPERATING MANUAL UPS MANUALE OPERATIVO UPS B9000FXS 60 80 100 125 160kVA ...
Page 2: ......
Page 5: ...Warnings and general information Avvertenze e informazioni generali 2 OMD10080 REV B ...
Page 96: ...UPS user manual Utilizzo dell UPS OMD10082 REV F 5 ENGLISH LANGUAGE ...
Page 142: ...UPS user manual Utilizzo dell UPS OMD10082 REV F 51 LINGUA ITALIANA ...