Installation and start-up of UPS B9000FXS
Installazione e avviamento B9000FXS
OMD10013 REV. I
11
Do not modify the device
Do not modify the device in any way: this may result in damage to the equipment
itself as well as to objects and persons. Maintenance and repair must be carried out
by authorized personnel only. Contact the manufacturer for details of the nearest
service centre.
2.3.5 Electrical connection
The UPS connection to the AC power must be carried out in compliance with the current
regulations.
Make sure the indications specified on the identification plate correspond to the AC power
system and to the actual electrical consumption of all of the equipment connected.
Check the conformity of the documentation
The UPS must be installed according to the requirements of HD 384.4.42 S1/A2 and
in compliance with standard CEI 60346-4-42.
Before connecting the unit to the distribution network, make sure you have received
the approval of the electrical power distribution Authority, so as provided for by the
current national regulations.
IT system
The UPS is also designed to be connected to an IT power distribution system.
All the electrical connections must be carried out by authorized personnel. Before connecting
the device make sure that:
the connection cable to the AC line is properly protected;
the nominal voltages, the frequency and the phase rotation of the AC supply are
respected;
the polarities of the DC cables coming from the battery have been checked;
no leakage current to earth is present.
The device is connected to the following voltage supplies:
DC battery voltage;
AC mains voltage;
AC bypass voltage.
Summary of Contents for ASD10
Page 1: ...OPERATING MANUAL UPS MANUALE OPERATIVO UPS B9000FXS 60 80 100 125 160kVA ...
Page 2: ......
Page 5: ...Warnings and general information Avvertenze e informazioni generali 2 OMD10080 REV B ...
Page 96: ...UPS user manual Utilizzo dell UPS OMD10082 REV F 5 ENGLISH LANGUAGE ...
Page 142: ...UPS user manual Utilizzo dell UPS OMD10082 REV F 51 LINGUA ITALIANA ...